PRODUCT DATA
68-0311-02
THX9321 Prestige
®
2.0 and
THX9421 Prestige
®
IAQ
with EIM
APPLICATION
The Prestige 2.0 and Prestige IAQ Systems feature an
effortless, 7-Day programmable color touchscreen thermostat
that provides control of temperature, humidification,
dehumidification, and ventilation for up to 4 Heat/2 Cool heat
pump systems or up to 3 Heat/2 Cool conventional systems
for residential and commercial applications.
FEATURES
RedLINK™ Compatible
Increase your content and profit per job by including
RedLINK™ accessories that meet your customers comfort
and convenience needs. RedLINK accessories include the
Wireless Outdoor Sensor, Portable Comfort Control (PCC),
Equipment Interface Module (EIM), RedLINK Internet
Gateway, Wireless Indoor Sensor, TrueSTEAM™ humidi-
fier with Wireless Adapter, TrueZONE™ zoning panel with
Wireless Adapter, Vent Boost Remote and Entry/Exit
Remote.
Customizable Service Reminders
Set up to 10 service reminders. Choose from the pre-set
options or customize your own. Reminders based on date
or the outdoor temperature.
Delta T Alerts and Diagnostics
Alerts give customers a sense of security while allowing
you to service or replace the equipment prior to a loss of
heating or cooling. Based on limits you set at installation,
customers can be alerted when their system is not operat-
ing as expected. The system alert will instruct customers to
contact you for assistance. Requires Equipment Interface
Module.
Delta T Installer Test
Save time by viewing Delta T while running a system test to
verify proper operation. Requires Equipment Interface
Module.
Universal Inputs
EIM - S1, S2, S3, S4
Assignable inputs allow you to setup Indoor and Outdoor
Temperature Sensors, Discharge and Return Air Sensors
or Dry Contact Devices. Dry Contact Devices can be used
to trip pre-set or customized alerts on the thermostat home
screen. Requires Equipment Interface Module.
Data Logs
The thermostat stores an Alerts Log, User Interactions Log
and a Performance Log to quickly determine if an issue is
caused by a system error or an accidental user error. Note:
The Performance Log only applies to the THX9421
thermostat.
Selectable for Residential and Light Commercial
Applications
One thermostat does it all to meet the needs of Residential
and Light Commercial applications. Simply select Residen-
tial or Commercial during the installer setup. If Commercial
is selected, the thermostat will use commercial language,
meet building codes and offer 365 day holiday scheduling.
USB Port for Quick Installer Setup
Save time by using a USB stick to upload installer settings,
and service reminders in one simple step.
Selectable Sensors
When paired with a Wireless Indoor Sensor(s) you have
the ability to choose which sensor(s) to use for tempera-
ture, humidification and dehumidification. They can be
used in combination for temperature averaging—or individ-
ually—to condition humidity levels in separate spaces.
THX9321 Prestige
®
2.0
THX9421 Prestige
®
IAQ with EIM
Page view 0
1 2 3 4 5 6 ... 159 160

Summary of Contents

Page 1 - THX9421 Prestige

PRODUCT DATA68-0311-02THX9321 Prestige® 2.0 and THX9421 Prestige® IAQ with EIMAPPLICATIONThe Prestige 2.0 and Prestige IAQ Systems feature an effortle

Page 2 - CONTENTS

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 10Installing Equipment Interface Module (if used)If no Equipment Interface Module i

Page 3 - SPECIFICATIONS

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 100HEAT PUMP AND BACKUP HEAT OPERATIONHeat pump with outdoor temperature lockoutsOu

Page 4 - 68-0311—02 4

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM101 68-0311—02Fossil Fuel Backup Heat (Backup Heat NOT Allowed to Run with Heat Pump)HEAT MODE

Page 5 - 5 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 102INDOOR AIR QUALITY (IAQ) CONTROLHumidificationThe thermostat reads the indoor hu

Page 6 - 68-0311—02 6

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM103 68-0311—022. If optional remote wireless indoor sensors are installed, you can choose whic

Page 7 - 7 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 1047. Set the desired lockout option. See Fig. 214.Fig. 214. NOTE: ISU 10140 gives

Page 8 - SYSTEM INSTALLATION

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM105 68-0311—02Dehumidification - ResidentialThe thermostat reads the indoor humidity level and

Page 9 - INSTALLATION OPTIONS

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 1065. Select whether the U1, U2, or U3 terminals are Normally Open or Normally Clos

Page 10 - Sensor Mounting Location

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM107 68-0311—024. Select the terminals wired to the Whole House Dehumid-ifier. See Fig. 225.Fig

Page 11

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 108Set up Dehumidification Away Mode1. Select Allowed at ISU 9180. See Fig. 231.Fig

Page 12 - Installing Wallplate

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM109 68-0311—02Dehumidification - CommercialThe thermostat reads the indoor humidity level and

Page 13 - THX9321 Installation

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM11 68-0311—02Selecting Return Air Temperature Sensor Mounting Location1. Install the Return Ai

Page 14 - ACCESSORIES

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 1102. If optional remote wireless indoor sensors are installed, you can choose whic

Page 15 - PERFORMING INITIAL SETUP

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM111 68-0311—022. If optional remote wireless indoor sensors are installed, you can choose whic

Page 16 - Linking RedLINK™ Accessories

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 112Dehumidification Away ModeDehumidification Away Mode for a commercial applicatio

Page 17 - Add Device

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM113 68-0311—02Ventilation Fan Control (ISU 10060)• Thermostat Controls FanThe thermostat turns

Page 18 - RedLINK Accessories

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 1144. Select the Ventilation Fan Control. See “Ventilation Fan Control (ISU 10060)”

Page 19 - TrueSTEAM

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM115 68-0311—028. If Percent On Time was selected for ISU 10050, select the Ventilation Percent

Page 20 - Dealer Informaon

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 1164. Press MORE SETTINGS to change maintenance reminders or set outdoor lockouts (

Page 21

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM117 68-0311—02Custom Reminders include:• Service Reminder— Set up for recurring or one time on

Page 22 - 68-0311—02 22

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 1187. The Fall Service Reminder will look like this on the Home Screen:Fig. 267. To

Page 23 - 23 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM119 68-0311—027. The preview of the custom reminder shows you what you’ve selected. Press Done

Page 24 - 68-0311—02 24

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 12Fig. 14. Installing Discharge and Return Air Temperature SensorsUse the following

Page 25 - 25 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 120Loading Dealer InformationPrestige thermostats can display the dealer’s contact

Page 26 - 68-0311—02 26

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM121 68-0311—02COMMERCIAL FEATURESThe thermostat can be setup for residential or light commerci

Page 27 - 27 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 122Setting custom events: commercial useThis feature lets you customize temperature

Page 28 - 68-0311—02 28

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM123 68-0311—024. Touch  or  to select the Heat and Cool temperatures.Fig. 290. 5. Review the

Page 29 - 29 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 124automatically adjust the ramp rate based on outdoor conditions. This allows the

Page 30 - 68-0311—02 30

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM125 68-0311—022. Select the terminals wired to the Remote Setback Dry Contact device (occupanc

Page 31 - 31 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 126Economizer and Time of Day (TOD) OperationEconomizerThe thermostat controls an e

Page 32 - 68-0311—02 32

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM127 68-0311—02Battery ReplacementWireless Indoor SensorReplace batteries in your indoor sensor

Page 33 - 33 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 128OPTIONAL ACCESSORIESPORTABLE COMFORT CONTROLIf you have only one thermostat, you

Page 34 - 68-0311—02 34

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM129 68-0311—02PORTABLE COMFORT CONTROLThe Portable Comfort Control communicates wirelessly wit

Page 35 - 1 to 12 CPH

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM13 68-0311—024. Remove the wallplate from the wall and, if drywall, drill two 3/16-in. holes i

Page 36 - 1 to 6 CPH

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 130REMOTE INDOOR SENSORSFor installation, see “Mounting C7189R1004 Wireless Indoor

Page 37

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM131 68-0311—02Temperature DisplayThe temperature reading displayed on the home screen is from

Page 38

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 132If you are sensing Humidity from two separate locations (one for humidification

Page 39

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM133 68-0311—02Calibration - Outdoor SensorThe C7089U1006 Outdoor Sensor is calibrated at the f

Page 40 - 0, 100 to 25,000 sec

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 134BACKUP CONTROLThis section explains when backup control is used. For example, if

Page 41 - 41 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM135 68-0311—02WIRINGSee Table 13 for Equipment Interface Module terminal descriptions and Tabl

Page 42 - 68-0311—02 42

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 136* Remove factory installed jumper for two transformer systems.†The THP9045A1023

Page 43 - 1° F/hr to 20° F/hr

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM137 68-0311—02Fig. 317. Inserting wires in thermostat terminal block.Fig. 318. Inserting wires

Page 44 - -20° F to 100° F

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 138EIM Wiring DiagramsTypical wiring of a conventional system with up to 3-stage he

Page 45

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM139 68-0311—02Typical wiring of a heat pump system with up to four-stage heat and two-stage co

Page 46 - 68-0311—02 46

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 14Mount Thermostat on WallplateAlign thermostat to wallplate and snap into place. S

Page 47 - 47 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 140Typical wiring for geothermal radiant heat, geothermal forced-air, and backup he

Page 48 - 68-0311—02 48

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM141 68-0311—02THX9321 Thermostat Wiring DiagramsTypical wiring of a 3-heat / 2-cool heat pump

Page 49 - 49 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 142THX9321 Thermostat Wiring Diagrams Using Universal Relays to Control Heating or

Page 50 - 68-0311—02 50

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM143 68-0311—02Fig. 328. 2-Wire Zone Valve with end switch.Fig. 329. Series 20 hot water heat.F

Page 51 - 51 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 144Fig. 332. Geothermal radiant heat with geothermal forced air and backup heat usi

Page 52 - 68-0311—02 52

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM145 68-0311—02Fig. 333. Wood stove-fired hot water fan coil with forced air furnace backup hea

Page 53 - 53 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 146Fig. 335. Hot water radiant heat with backup forced air heat. Zoned with forced

Page 54 - 68-0311—02 54

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM147 68-0311—02Fig. 336. Hot water radiant heat with backup forced air heat. Zoned with forced

Page 55 - 55 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 148Fig. 338. Wood stove with heat pump and backup electric strips. (For application

Page 56 - 68-0311—02 56

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM149 68-0311—02Wiring IAQ Equipment or a Heat/Cool Stage to the Universal TerminalsTo Equipment

Page 57 - 57 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM15 68-0311—02TrueSTEAM1. Wire and power TrueSTEAM.2. Connect the ABCD terminals between TrueST

Page 58 - 68-0311—02 58

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 150Fig. 345. Connecting a stage of heating or cooling to a universal relay (U1, U2,

Page 59 - 59 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM151 68-0311—02Economizer Module Wiring DiagramsTypical wiring of a W7220 Economizer Module for

Page 60 - 68-0311—02 60

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 152Typical wiring of a W7213/W7214 Economizer Module for a heat pump system, using

Page 61 - 61 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM153 68-0311—02Wiring C7089U1006 Outdoor SensorCAUTIONElectrical Interference (Noise) Hazard.Ca

Page 62 - 68-0311—02 62

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 154Wiring guide — Wired Indoor SensorsUse the S1, S2, S3, or S4 terminals for wired

Page 63 - 63 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM155 68-0311—02ZONINGThe following diagrams show the wiring for zoning with different IAQ equip

Page 64 - 68-0311—02 64

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 156Zoning and HumidificationFig. 356. Prestige IAQ controlling one zone with an HZ4

Page 65 - 65 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM157 68-0311—02Zoning and VentilationFig. 357. Ventilation with zoning.Setting up Ventilation C

Page 66 - 68-0311—02 66

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 158Zoning FAQsQ: How does the Prestige or Prestige IAQ thermostat control a humidif

Page 67 - 67 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM159 68-0311—02TROUBLESHOOTINGREGULATORY INFORMATIONFCC Compliance Statement (Part 15.19) (USA

Page 68 - INSTALLER TESTS

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 162. Follow the prompts on the thermostat screen until you reach the Wireless Setup

Page 69 - Using the Equipment Test

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIMAutomation and Control SolutionsHoneywell International Inc.1985 Douglas Drive NorthGolden Val

Page 70 - Mounting Optional Accessories

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM17 68-0311—02Completing Initial Setup5. Finish the setup by selecting the desired options. Tou

Page 71 - 71 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 186. Press and quickly release the CONNECT button on each new RedLINK accessory.NOT

Page 72 - OPERATION

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM19 68-0311—02ERROR MESSAGES:E1 29: Incompatible device cannot be connected.E1 34: Low RF signa

Page 73 - Setting system mode

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 2ORDERING INFORMATIONWhen purchasing replacement and modernization products from yo

Page 74 - / Edit Schedule

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 203. Type the sensor name and press Done. The sensor names are used when selecting

Page 75 - Permanent Hold

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM21 68-0311—02Installer OptionsThe following options are available when you access Installer Op

Page 76

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 22Table 4. Installer Setup (ISU) Table.ISU NumberInstaller Setup Name Settings Defa

Page 77

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM23 68-0311—021060 Outdoor Air SensorNoYesNo Both No This ISU automatically defaults to Yes whe

Page 78

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 242010 Heating Equipment TypeConventional Forced Air Heat:Standard Efficiency Gas F

Page 79 - 79 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM25 68-0311—022050 Geothermal Forced Air SystemNoneUsed for Cooling OnlyUsed for Heating and Co

Page 80 - Automac

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 262090 What Terminals are Wired to Cool - Stage 4?NoneU1U2U3Default varies based on

Page 81 - 81 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM27 68-0311—022130 Backup Heat Stages0 - 21 Both No This ISU is only displayed when a backup he

Page 82 - Setting preferences

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 282170 What Terminals are Wired to Backup Heat - Stage 2?NoneU1U2Default varies bas

Page 83 - Viewing dealer information

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM29 68-0311—022210 Backup Heat Fan OperationNo FanEquipment Controls FanThermostat Controls Fan

Page 84 - Utility Scheduling

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM3 68-0311—02SPECIFICATIONSThermostat Description:Electrical Ratings for:Equipment Interface Mo

Page 85 - Advanced Features

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 303000 ChangeoverManual AutomaticManual:if ISU 1010 is ResidentialAutomatic:if ISU

Page 86 - (U1, U2, U3)

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM31 68-0311—023020 Finish With High Cool StageNo YesNo Both No ISU 3010 Temperature Control Opt

Page 87 - ALERTS AND DIAGNOSTICS

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 323030 Staging Control - Cool Differential Stage 4Comfort 1.0° F to 4.5° F from set

Page 88 - 68-0311—02 88

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM33 68-0311—023050 Staging Control - Heat Differential Stage 3Note: Depending on the applicatio

Page 89 - Run a Test for Each Stage

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 343080, 3090Staging Control - Backup Heat Differential Stage 1Note: “Stage 1"

Page 90 - Delta T Alerts

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM35 68-0311—023120 Outdoor Temperature Lockouts:Compressor Lockout / Balance PointOff 5° F to 6

Page 91 - Data Logs

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 363130 Radiant Heat Cycles Per Hour - Stage 21 to 12 CPH3 Both No ISU 3010 Temperat

Page 92 - Alerts Log

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM37 68-0311—023140 Cool Cycles Per Hour - Stage 31 to 6 CPH3 Commercial No ISU 3010 Temperature

Page 93 - Performance Logs

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 383150 Heat Cycles Per Hour - Stage 1Note: Depending on the application, the text d

Page 94 - Using the Performance Logs

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM39 68-0311—023150 Heat Cycles Per Hour - Stage 3Note: Depending on the application, the text d

Page 95 - Dry Contact Alerts

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 4Fig. 1. Dimensions of THX9421 Prestige IAQ thermostat in in. (mm).Fig. 2. Dimensio

Page 96 - Set Up the Dry Contact Alerts

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 403160 Backup Heat Cycles Per Hour - Stage 21 to 12 CPHDefault varies based on heat

Page 97 - Staging Control

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM41 68-0311—023200 Heating Throttling Range1° F to 30° F 2° F Commercial No The default Heatin

Page 98 - Cool Differential

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 424020 Type of OverrideStandardInitiate OccupancyStandard Commercial No Standard:Th

Page 99 - Multistage Control

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM43 68-0311—024050 Outdoor Temperature used with Minimum Heat Recovery Ramp RateOff-20° F to 10

Page 100 - Geothermal Radiant Heat

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 444060 Outdoor Temperature used with Maximum Heat Recovery Ramp RateOff-20° F to 10

Page 101 - 101 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM45 68-0311—024070 Outdoor Temperature used with Minimum Cool Recovery Ramp RateOff-20° F to 10

Page 102 - INDOOR AIR QUALITY (IAQ)

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 464080 Outdoor Temperature used with Maximum Cool Recovery Ramp RateOff-20° F to 10

Page 103 - 103 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM47 68-0311—024120 Residential:Entry / Exit Remote - Home Heat SetpointCommercial:Entry / Exit

Page 104 - Control Humidification Level

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 485000 What Sensors are WIRED to your System?Check box on screen for each:Indoor Ai

Page 105 - 105 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM49 68-0311—025040 Which Sensors will be used for TEMPERATURE Control? (Multiple Sensors are Av

Page 106 - Dehumidifier

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM5 68-0311—02Table 1. Prestige Kits.KitPart NumberIncluded in KitPart Number DescriptionPrestig

Page 107 - Dehumidification Away Mode

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 506000 Select the Dry Contacts in the SystemCheck box on screen for each:Remote Set

Page 108 - 68-0311—02 108

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM51 68-0311—026040 Remote Setback - Standby Heat Setpoint50° F to 70° F64° F Commercial Yes Re

Page 109 - Dehumidification - Commercial

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 526100 Water Leak Alert Dry Contact SetupNormally OpenNormally ClosedNormally Open

Page 110 - 68-0311—02 110

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM53 68-0311—026160 Fan Failure Alert Dry Contact SetupNormally Open when Fan is Running Normall

Page 111 - 111 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 547110 Air Filter 1 Replacement ReminderNote: “1” is not displayed if there is only

Page 112 - Ventilation

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM55 68-0311—028050 Humidification - Window ProtectionOffOnOff Both No Requires an optional outd

Page 113 - 113 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 568100 Clean Tank / Water Filter Replacement ReminderOff60 Run Time Days90 Run Time

Page 114 - 68-0311—02 114

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM57 68-0311—029040 What Terminals are Wired to A/C with Low Speed Fan?What Terminals are Wired

Page 115 - Control Ventilation Level

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 589080 Dehumidification ControlBasicMinimum On TimeHigh Humidity Comfort ResetHigh

Page 116 - CUSTOMIZABLE REMINDERS

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM59 68-0311—029130 Dehumidifier Fan ControlThermostat Controls FanEquipment Controls FanThermos

Page 117 - Custom Reminders include:

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 6 Table 2. Thermostat Replacement Parts and Accessories.Product Part NumberOperatin

Page 118 - 68-0311—02 118

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 6010000 Ventilation TypeNone ERV / HRVPassive (Fan Only)Fresh Air DamperNone Both N

Page 119 - Load Installer Setup

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM61 68-0311—0210120 Ventilation Percent On Time10% to 100% (in 10% increments)30% Both No The t

Page 120 - (Prestige IAQ Only)

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 6210130 Ventilation High Temperature LockoutOff80° F to 110° F (in 5° F increments)

Page 121 - / Event Scheduler

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM63 68-0311—0211050 UV Bulb 2 Replacement ReminderOff, 6, 12, 24 Calendar MonthsOff Both No1200

Page 122 - Setting holiday schedule:

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 6413030 Allow Delta T Diagnostics During DehumidificationNoYesYes Both Yes This ISU

Page 123 - Press to start

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM65 68-0311—0213080 Allow Heat Delta T Diagnostics when Outdoor Humidity is [Outdoor Humidity R

Page 124 - Remote Setback

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 6613130 Allow Cool Delta T Diagnostics when Indoor Temperature is [Indoor Temperatu

Page 125 - 125 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM67 68-0311—0213170 Defrost CycleNone1 to 60 minutes (in 1 minute increments)10 Both Yes This I

Page 126 - Pre-Occupancy Purge

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 68INSTALLER TESTSUse the installer tests to check out the system:• Equipment Test:

Page 127 - Battery Replacement

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM69 68-0311—02Using the Equipment Test1. Press Equipment Test on the Installer Test screen (see

Page 128 - OPTIONAL ACCESSORIES

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM7 68-0311—02* Prestige IAQ Kits and YTHM5421R1010 Kit include 50062329-001 Discharge/Return Ai

Page 129 - PORTABLE COMFORT CONTROL

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 70Mounting Optional AccessoriesMounting Outdoor SensorMount the sensor where:• it c

Page 130 - REMOTE INDOOR SENSORS

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM71 68-0311—02Mounting C7189U1005 Wired Indoor SensorUse the following steps to mount the senso

Page 131 - Humidity Display

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 72OPERATIONFig. 73. Quick reference to residential display.Fig. 74. Quick reference

Page 132 - 68-0311—02 132

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM73 68-0311—02Setting the time/date1. Touch the current time. The screen displays Set Time/Set

Page 133 - Calibration - Indoor Sensor

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 74Preset Energy-Saving SchedulesThis thermostat uses default Energy Saver settings

Page 134 - INTERFACE MODULE

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM75 68-0311—02Overriding schedules: residential use1. Touch  or  to adjust the temperature (r

Page 135 - 135 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 763. Touch  or  to view the status of all the equipment your thermostat is contro

Page 136 - 68-0311—02 136

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM77 68-0311—02Setting custom events: commercial useThis feature lets you customize temperature

Page 137 - 137 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 784. Touch  or  to select the Heat and Cool temperatures.Fig. 105. 5. Review the

Page 138 - EIM Wiring Diagrams

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM79 68-0311—02Depending on how your thermostat was installed, it may delay for up to 30 minutes

Page 139 - 139 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 8SYSTEM INSTALLATIONWhen Installing this Product...1. Read these instructions caref

Page 140 - 68-0311—02 140

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 80Adjusting dehumidification settings: commercial useThis feature can control a deh

Page 141 - 141 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM81 68-0311—024. If you select a predefined screen color, check the left side of the screen to

Page 142 - 68-0311—02 142

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 829. Touch Make Additional Adjustments to continue mak-ing changes, or touch Accept

Page 143 - 143 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM83 68-0311—02Adjusting security settingsYou can adjust security options to prevent unauthorize

Page 144 - 68-0311—02 144

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 841. Press MENU2. Scroll to select TEMPORARY SCHEDULE3. Select option, then follow

Page 145 - 145 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM85 68-0311—02Advanced FeaturesADAPTIVE INTELLIGENT RECOVERY (RESIDENTIAL USE ONLY)Over time, t

Page 146 - IAQ WITH EIM

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 86Installer optionsInstaller Options require a password and should only be changed

Page 147 - 147 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM87 68-0311—02UNIVERSAL INPUTS (S1, S2, S3, S4)S1, S2, S3, and S4 are universal inputs that can

Page 148 - 68-0311—02 148

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 887. Delta T Diagnostics is only for non-zoned forced air systems.8. The thermostat

Page 149 - To Equipment Interface Module

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM89 68-0311—025. For Air-to-Air Heat Pumps, press the up/down arrows to set the maximum time du

Page 150 - 68-0311—02 150

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM9 68-0311—02INSTALLATION OPTIONSThe THX9321 Prestige® 2.0 thermostat is wired directly to the

Page 151 - W7220 Economizer Module

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 90Set Delta T Limits1. Press Stage 1 to set the limits and run time (see Fig. 158).

Page 152 - 68-0311—02 152

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM91 68-0311—02Delta T Alerts are also displayed for performance related issues such as dirty ai

Page 153 - 153 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 92Alerts LogThe Alerts Log stores a history of the most recent 25 alerts and record

Page 154 - 68-0311—02 154

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM93 68-0311—02User Interactions LogThe User Interactions Log can help a service technician save

Page 155 - 155 68-0311—02

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 94Using the Data LogsTO ACCESS THE DATA LOGS1. From the Home screen, press Menu.2.

Page 156 - Zoning and Humidification

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM95 68-0311—024. Select the desired time period at the top of the screen (Hourly, Daily, Weekly

Page 157 - Zoning and Ventilation

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 96When the user presses the alert for more info, the Notification screen is display

Page 158 - Zoning FAQs

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM97 68-0311—021. Wire the dry contact device to S1, S2, S3, or S4 termi-nals at the EIM.2. Ente

Page 159 - REGULATORY INFORMATION

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM68-0311—02 98Cool DifferentialThe indoor temperature must rise to the selected differential se

Page 160 - Printed in United States

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ WITH EIM99 68-0311—022. Default is Comfort. Adjust differentials as needed.Fig. 195. Backup Heat Upsta