VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROL
69-0625—03 2
INSTALLATION
When installing this product ...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and on
the product to ensure the product is suitable for
your application.
3. Ensure installer is a trained, experienced service
technician.
4. After installation is complete, use these instructions
to check out product operation.
WARNING
Fire or explosion hazard. Can cause property
damage, severe injury, or death.
Follow these warnings exactly:
1. Disconnect power supply before wiring to
prevent electrical shock or equipment damage.
2. To avoid dangerous accumulation of fuel gas,
turn off gas supply at the appliance service
valve before starting installation, and perform
the gas leak test after completion of installation.
3. Do not bend pilot tubing at gas control or pilot
burner after compression fitting has been
tightened, or gas leakage at the connection
may result.
4. Always install sediment trap in gas supply line
to prevent contamination of gas control.
5. Do not force the gas control knob. Use only
your hand to turn the gas control knob. Never
use tools. If the gas control knob will not
operate by hand, the gas control should be
replaced by a qualified service technician.
Force or attempted repair may result in fire or
explosion.
CAUTION
Never apply a jumper across or short the valve
coil terminals. This may burn out the heat
anticipator in the thermostat or damage the
electronic intermittent pilot (IP) module.
IMPORTANT
These gas controls are shipped with protective
seals over inlet and outlet tappings. Do not
remove the seals until you are ready to connect
piping.
Follow the appliance manufacturer’s instruc-
tions if available; otherwise, use the instructions
provided below.
Converting Between Natural and
LP Gas
WARNING
Fire or explosion hazard. Can cause property
damage, severe injury, or death.
Do not attempt to use a gas control set for
natural gas on LP gas or a gas control set for
LP gas on natural gas.
To convert a gas control from natural gas to LP gas or
from LP gas to natural gas, contact your Honeywell
representative.
Standard- or slow-opening gas controls are converted
from one gas to another with a conversion kit (order
separately). Order Part Number 393691 to convert from
natural to LP gas. Order Part Number 394588 to convert
from LP to natural gas. Step-opening gas controls cannot
be converted.
Install Adapters to Gas Control
Install adapters to the gas control as follows:
Flanges
1. Choose the appropriate flange for your application.
2. Remove the seal over the gas control inlet or outlet.
3. Ensure the O-ring is fitted in the groove of the
flange. If the O-ring is not attached or is missing, do
not use the flange.
4. With the O-ring facing the gas control, align the
screw holes on the gas control with the holes in the
flange. Insert and tighten the screws provided with
the flange. See Fig. 1. Tighten the screws to 25 in.
pounds of torque to provide a gas-tight seal.
Fig. 1. Install flange to gas control.
Bushings
1. Remove the seal over the gas control inlet or outlet.
2. Apply moderate amount of good quality pipe com-
pound to the bushing, leaving two end threads bare.
On LP installation, use a compound resistant to LP
gas. Do not use Teflon tape.
3. Insert the bushing into the gas control and thread
the pipe carefully into the bushing until tight.
Using Adapters to Solve Swing
Radius Problems
In some field service applications, it is difficult or
impossible to thread the gas control onto the gas supply
pipe because of space limitations. This problem can be
resolved in many instances by using an adapter. The
adapter is installed on the end of the supply pipe in place
of the gas control, following the same precautions and
instructions that are used for installing the gas control.
After the adapter is installed, the gas control is attached to
the adapter as outlined above. Note that using an adapter
increases the overall length of the gas control.
M3087
GAS CONTROL OUTLET
FLANGE
9/64 INCH HEX
SCREWS (4)
1 DO NOT OVERTIGHTEN SCREWS.
TIGHTEN TO 25 INCH POUNDS.
1