M2985768-0171-12HR150, 200; ER150, 200 Perfect Window™ Fresh Air Ventilation SystemsPRODUCT DATA Included In thIs VentIlatIon system BoxTools and acce
GETTING STARTED40 IN. (1m) MINIMUMCOLD AIRRETURNFORCED AIRFURNACECOMBUSTION OR ELECTRICM6548ERETURNAIROUTDOORSNOTES:1.2.3.4.FURNACE BLOWER IS REQUIRED
GETTING STARTEDBalancing AirflowBalancing the airflow verifies that the Fresh Air Ventilation System is delivering the intended airflow and energy perform
MOUNTINGWhen Installing this Product…1. Read these instructions carefully. Failure to follow these instructions could damage the product or cause a ha
PLUMBINGInstalling Drain Line and P-TrapM6552DRAIN PANO RINGHR BOTTOMWASHERNUTInstalling drain line.Fig. 8. There are two holes at the bottom of the v
WIRINGWIRINGCAUTION: Electrical shock hazard. Can cause personal injury.Be sure ventilator is correctly grounded. Confirm polarity of power line switch
WIRING12345678910VNTLOWREDYELGRNVNT HIGFRGTDSTATM29844 JUMPER BETWEEN VNT COM AND RED. CHOOSE AMONG AVAILABLE CONTROLS. ALL WIRE IDENTICALLY.1122VI
WIRING12345678910VNTLOWVNTCOMREDYELGRNVNT HIGFRGTDSTATM29848 JUMPER BETWEEN VNT COM AND RED. JUMPER BETWEEN DHM2 AND VNT1. 1122DHM 1DHM 2VNT 1VNT 2
WIRINGLEGENDHIGH VOLTAGE12V LOW VOLTAGEM29742K7K2 K3P2REDTHERMISTOR(NOT ON ALL UNITS)BLACKGREENNEUTRALLINEAUTO-TRANSFORMERSEEDEFROSTDETAILWHITEP4BLUEK
DUCTINGAirflow BalancingVolume-balanced airflow in the ventilator is required. Volume of outside air brought in must equal the volume of air the unit ex
APPENDICESWhen the ventilator is powered up it will go through a self-test and turn on both fan speeds and check damper operation.LED on Terminal Boar
APPENDICESTable 1. Troubleshooting Guide.Symptom Cause SolutionPoor airflow Plugged outside hood 1/4 in. (6 mm) mesh.• Clean exterior hoods or vents•
APPENDICESSymptom Cause SolutionHumidity levels are too high; condensation appears on windowsDehumidistat is set too high. Set dehumidistat lower.Unde
APPENDICESPARTS LISTHR/ER Parts ListItem Number (Fig. 21)Part Number for DescriptionHR150B/HR200BER150B/ER200BER150C/ER200C1 209746 Heat Transfer Cor
APPENDICESM298552 379845 611HR150/HR200 and ER150/ER200 exploded view of parts keyed to HR/ER Parts List.Fig. 21. HR150, 200; ER150, 200 Perfect Windo
APPENDICESIMPORTANTThe specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit might not exactly
APPENDICESHR150 and HR200 Ventilation performance.Fig. 22. M29743B255075100125150175.1.2.3.4.5.6.78377736758471817716415614312310038EXT STATICPRESSURE
APPENDICESER150 and ER200 Ventilation performance.Fig. 24. ER150 and ER200 dimensions in in. (mm).Fig. 25. HIGH SPEEDLOW SPEED220200180160140120100806
Automation and Control SolutionsHoneywell International Inc.1985 Douglas Drive NorthGolden Valley, MN 55422Honeywell Limited–Honeywell Limitée35 Dynam
Perfect Window Fresh Air Ventilation Systems NEED HELP? For assistance with this product please visit http://yourhome.honeywell.com or call Honeyw
GETTING STARTEDSafety Definitions and PrecautionsSafety DefinitionsThese safety terms identify information you must read. CAUTION: Indicates a hazardous
GETTING STARTEDThe HR150B and HR200B Perfect Window™ Fresh Air Ventilation Systems provide proper levels of ventilation with energy savings by transfe
GETTING STARTEDThe Fresh Air Ventilation System is designed to supply fresh air and exhaust stale air. The system draws fresh outdoor air through the
GETTING STARTEDSizingASHRAE 62.2There are several methods that can provide satisfactory results for sizing a ventilator to provide adequate ventilatio
GETTING STARTEDMounting Position and LocationThe HR150/ER150 and HR200/ER200 can be suspended from exposed ceiling joists, ceiling surface or floor mou
GETTING STARTEDDesign and installation of ductwork must be according to standard HVAC practice to deliver required quantities of fresh air to temperat