PRODUCT DATA
Put UPC Code Here
68-0291-03
®
Automatic Ignition Systems
ANSI Z21.20
Y8610U Intermittent Pilot Retrofit Kit
GENERAL
The Y8610U is a complete kit for converting conventional
standing pilot systems to intermittent pilot systems. It is used
on gas-fired atmospheric furnaces, boilers, and heating
appliances. Not for use on direct vent, induced draft, or power
burner equipment. Meets ANSI Z21.71 standard for automatic
intermittent pilot ignition systems on central furnaces and
boilers.
FEATURES
Y8610U kits can be used with either natural or LP gas.
The S8610U ignition control provides a 90 second
maximum ignition trial, shuts off, waits five minutes
nominal, then re-initiates the pilot ignition sequence. The
ignition trial, shutoff, and wait cycle repeat until the pilot
lights or the call for heat ends.
Each kit includes:
S8610U Intermittent Pilot Module
VR8304M Dual Valve Combination Gas Control
or
VR8204A Dual Valve Combination Gas Control
392431 Igniter-Sensor
394800-30 Ignition Cable
393691 Natural to LP Gas Conversion Kit
Wiring Harness
393690-14 Straight Flange Kit (3/4 in.)
Reducer adapters for gas control with VR8304M
Installation hardware
Temperature Ratings:
S8610U: -40°F to 165°F (-40°C to 74°C)
VR8304M: -40°F to 175°F (-40°C to 79°C)
VR8204A: 0°F to 175° F (-18°C to 79°C)
Intermittent Pilot Gas Ignition Control Module
Uses flame rectification for flame sense
Internal spark generator lights pilot gas; main burner lights
after pilot flame lights and proves
100% shutoff of pilot and main gas if burner fails to light
Continuous retry ignition sequence prevents nuisance
lockouts
Two LEDs indicate system status and flame signal strength
Gas Control Valve
Straight through body pattern
VR8304M capacity is 270 ft
3
/hr (7.6 m
3
/hr)
VR8204A capacity with or without 1/2” x 3/4” adapter is
150 ft
3
/hr (4.2 m
3
/hr)
Manual ON-OFF valve blocks gas flow into the gas control
when in the OFF position
Two main automatic valves: one solenoid-operated, and
one a servo-operated diaphragm system
Igniter-Sensor
Single electrode made of Kanthal provides both ignition
and flame sensing
Rated for 1775°F (968°C) at electrode tip; 1250°F (677°C)
at ceramic insulator
Contents
General .............................................................................1
Specifications ...................................................................2
Planning the Installation ....................................................6
Installation ........................................................................7
Settings ............................................................................14
Checkout ..........................................................................15
Operation ..........................................................................16
Troubleshooting ................................................................17
Ansi Standards .................................................................22
Page view 0
1 2 3 4 5 6 ... 23 24

Summary of Contents

Page 1 - FEATURES

PRODUCT DATAPut UPC Code Here68-0291-03®Automatic Ignition SystemsANSI Z21.20Y8610U Intermittent Pilot Retrofit KitGENERALThe Y8610U is a complete kit

Page 2 - SPECIFICATIONS

Y8610U INTERMITTENT PILOT RETROFIT KIT68-0291—03 10Install the Gas ControlWARNINGFIRE OR EXPLOSION HAZARDCAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR

Page 3 - Igniter-Sensor Specifications

Y8610U INTERMITTENT PILOT RETROFIT KIT11 68-0291—03Fig. 11. Install sediment trap.Mount Gas Control1. The gas control can be mounted from 0 to 90 degr

Page 4 - 68-0291—03 4

Y8610U INTERMITTENT PILOT RETROFIT KIT68-0291—03 12Locate and Mount the S8610U Intermittent Pilot ModuleLocationIdentify a mounting location for the S

Page 5 - 5 68-0291—03

Y8610U INTERMITTENT PILOT RETROFIT KIT13 68-0291—03Connect Ignition CableUse the provided ignition cable to connect the S8610U module to the pilot bur

Page 6 - PLANNING THE INSTALLATION

Y8610U INTERMITTENT PILOT RETROFIT KIT68-0291—03 14Fig. 16. Y8610U connections in a heating system with an atmospheric burner and no vent damper.SETTI

Page 7 - INSTALLATION

Y8610U INTERMITTENT PILOT RETROFIT KIT15 68-0291—03JumperThis jumper (labeled P4) is used to lock the operating sequence selected by the DIP switch se

Page 8 - Check Appliance Wiring

Y8610U INTERMITTENT PILOT RETROFIT KIT68-0291—03 167. Perform a gas leak test in the appliance including both the inlet and outlet sides of the gas co

Page 9 - Remove Thermocouple

Y8610U INTERMITTENT PILOT RETROFIT KIT17 68-0291—03TROUBLESHOOTINGWARNINGFire, Explosion, or Electrical Shock Hazard.Can cause severe injury, death or

Page 10 - Install Gas Control Piping

Y8610U INTERMITTENT PILOT RETROFIT KIT68-0291—03 18STEP 4: Check Pilot and Main Burner Lightoff.1. Set the thermostat to “Call for Heat.”2. Watch the

Page 11 - Connect Pilot Gas Tubing

Y8610U INTERMITTENT PILOT RETROFIT KIT19 68-0291—03LED Status and TroubleshootingThe ignition control module has two LEDs; one for flame sensing and o

Page 12 - Wire the System

Y8610U INTERMITTENT PILOT RETROFIT KIT68-0291—03 2ORDERING INFORMATIONWhen purchasing replacement and modernization products from your TRADELINE® whol

Page 13 - Connect Ignition Cable

Y8610U INTERMITTENT PILOT RETROFIT KIT68-0291—03 20aFlash Code Descriptions:- Flash Fast: rapid blinking.- Heartbeat: Constant ½-second bright, ½-seco

Page 14 - SETTINGS

Y8610U INTERMITTENT PILOT RETROFIT KIT21 68-0291—03 Troubleshooting GuideRefer to the Fig. 22 for troubleshooting the S8610U control module.Fig. 22. T

Page 15 - CHECKOUT

Y8610U INTERMITTENT PILOT RETROFIT KIT68-0291—03 22ANSI STANDARDSExhibit ARecommended Procedure for Safety Inspectionof an Existing Appliance Installa

Page 16 - OPERATION

Y8610U INTERMITTENT PILOT RETROFIT KIT23 68-0291—03Exhibit BProcedure for Installing Automatic Intermittent Pilot SystemsPrior to beginning this proce

Page 17 - TROUBLESHOOTING

Y8610U INTERMITTENT PILOT RETROFIT KITAutomation and Control SolutionsHoneywell International Inc.1985 Douglas Drive NorthGolden Valley, MN 55422Hone

Page 18 - Lightoff

Y8610U INTERMITTENT PILOT RETROFIT KIT3 68-0291—03Transformer Sizing:Add current ratings of Y8610, vent damper, and any other control system component

Page 19 - STATUS LED

Y8610U INTERMITTENT PILOT RETROFIT KIT68-0291—03 4Fig. 1. Y8610U retrofit kit components.Fig. 2. S8610U module dimensions in inches (mm).VR8304S8610U

Page 20 - 68-0291—03 20

Y8610U INTERMITTENT PILOT RETROFIT KIT5 68-0291—03Fig. 3. VR8304M mounting dimensions in inches (mm).Fig. 4. VR8204A mounting dimensions in inches (mm

Page 21 - Troubleshooting Guide

Y8610U INTERMITTENT PILOT RETROFIT KIT68-0291—03 6Fig. 5. 392431 Igniter-sensor mounting dimensions in inches. (mm).PLANNING THE INSTALLATIONWARNINGFi

Page 22 - ANSI STANDARDS

Y8610U INTERMITTENT PILOT RETROFIT KIT7 68-0291—03INSTALLATIONWhen Installing this Product…1. Read these instructions carefully. Failure to follow the

Page 23 - Exhibit B

Y8610U INTERMITTENT PILOT RETROFIT KIT68-0291—03 85. Applicable only to warm air heating appliances. Inspect heat exchangers for cracks, openings or e

Page 24 - Printed in U.S.A

Y8610U INTERMITTENT PILOT RETROFIT KIT9 68-0291—03Remove ThermocoupleUnscrew or snap the thermocouple out of the pilot burner and discard. See Fig. 7.