USER MANUALPut Bar Code Here66-2066-01P520 Signal ProcessorAPPLICATIONThe Honeywell P520 is a rack mounting signal processor that is compatible with v
P520 SIGNAL PROCESSOR66-2066—01 10TROUBLESHOOTINGModule CommunicationsThe P520 communicates with any host computer that has a USB port and supports AS
P520 SIGNAL PROCESSOR11 66-2066—01To change or check the station number of the P520, proceed as follows:1. Press and hold the Reset button for 4 secon
P520 SIGNAL PROCESSOR66-2066—01 12address 2). To change to 9600 baud, increase the display past 4863. The next display will be 9600, which is 9600 bau
P520 SIGNAL PROCESSOR13 66-2066—01Fig. 8. P520 with S550B/BE programming flowchart.PRESS BOTH A & B BUTTONS“CAL?”CALIBRATE VIEWINGHEAD? NN “CALU”A
P520 SIGNAL PROCESSOR66-2066—01 14Fig. 9. P520 with S552B/BE programming flowchart.PRESS BOTH A & B BUTTONS“CAL?”CALIBRATE VIEWINGHEAD? NNNORMAL O
P520 SIGNAL PROCESSOR15 66-2066—01Fig. 10. P520 with S556B/BE programming flowchart.PRESS BOTH A & B BUTTONS“CAL?”CALIBRATE VIEWINGHEAD? NN “CALU”
P520 SIGNAL PROCESSORAutomation and Control SolutionsHoneywell International Inc.1985 Douglas Drive NorthGolden Valley, MN 55422customer.honeywell.co
P520 SIGNAL PROCESSOR66-2066—01 2Fig. 1. P520 front faceplate dimensions.Fig. 2. P520 side view dimensions.INSTALLATIONWhen Installing this Product…1.
P520 SIGNAL PROCESSOR3 66-2066—013. Install a ground wire from the ignition transformer case to the igniter assembly.4. Ensure all igniter wires and c
P520 SIGNAL PROCESSOR66-2066—01 4Fig. 3. Rear PCB terminal wiring.Polarity must be observed when wiring this connection (the positive terminal is on t
P520 SIGNAL PROCESSOR5 66-2066—01Wiring the Viewing HeadWiring of the viewing head is made to the terminals on the rear backplane PCB. These terminals
P520 SIGNAL PROCESSOR66-2066—01 6IMPORTANTSource impedance resistor required at the signal processor between SC and SIG GND terminals for proper signa
P520 SIGNAL PROCESSOR7 66-2066—01Verifying the validity of the gain code received is one of the tasks performed by the processor in the viewing heads.
P520 SIGNAL PROCESSOR66-2066—01 8change the displayed value. Once the desired value is displayed, press the STORE button. When the set point is stored
P520 SIGNAL PROCESSOR9 66-2066—01SETUP AND ADJUSTMENT PROCEDURESSighting AdjustmentBefore making definitive settings (i.e., establishing the set point