BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS
63-4523—01 14
Objects Table
Table 5. Objects
Object Name
Type and
Instance
Object Property
TB7600A5x14B
TB7652A5x14B
TB7600B5x14B
TB7652B5x14B
TB7605B5x14B
TB7656B5x14B
TB7607B5x14B
TB7657B5x14B
TB7600H5x14B
TB7652H5x14B
Room Temperature AV 7 Present_Value (R,W) √√√√√√√√√√
Room Temp Override BV 8 Present_Value (R,W) √√√√√√√√√√
Outdoor Temperature AV 9 Present_Value (R,W) √√√√√√√√√√
Outdoor Temp Override BV 10 Present_Value (R,W) √√√√√√√√√√
Room Humidity AV 11 Present_Value (R) √√
Occupancy Command MV 12 Present_Value (R,W) √√√√√√√√√√
System Mode HP MV 13 Present_Value (R,W) √√
System Mode RTU MV 14 Present_Value (R,W) √√√√√√√√
Fan Mode MV 15 Present_Value (R,W) √√√√√√√√√√
Supply Temp AI 16 Present_Value (R) √√√√√√ √√
Supply RH AV 17 Present_Value (R) √√
Keypad Lockout MV 18 Present_Value (R,W) √√√√√√√√√√
Control Output GR 19 Present_Value (R)
PI Heating Demand AV 20 Present_Value (R) √√√√√√√√√√
PI Cooling Demand AV 21 Present_Value (R) √√√√√√√√√√
Economizer Output AV 22 Present_Value (R) √√
Controller Status GRP 23 Present_Value (R)
AUX BI 24 Present_Value (R) √√√√√√√√√√
G Fan BI 25 Present_Value (R) √√√√√√√√√√
Y1 Cool BI 26 Present_Value (R) √√√√√√√√√√
Y2 Cool BI 27 Present_Value (R) √√√√√√√√
W1 Heat BI 28 Present_Value (R) √√√√√√√√√√
W2 Heat BI 29 Present_Value (R) √√√√√√
Reversing Valve BI 30 Present_Value (R) √√
DI 1 Status BI 31 Present_Value (R) √√√√√√√√√√
DI 2 Status BI 32 Present_Value (R) √√√√√√ √√
Local Motion BI 33 Present_Value (R) √√√√√√√√√√
Effective Occupancy MV 34 Present_Value (R) √√√√√√√√√√
Controller Alarms GRP 35 Present_Value (R)
Frost Alarm BI 36 Present_Value (R) √√√√√√√√√√
Clock Alarm BI 37 Present_Value (R) √√√√√
Filter Alarm BI 38 Present_Value (R) √√√√√√√√√√
Service Alarm BI 39 Present_Value (R) √√√√√√√√√√
Fan Lock Alarm BI 40 Present_Value (R) √√√√√√√√√√
Temperature Setpoints GRP 41 Present_Value (R)
Occupied Heat Setpoint AV 42 Present_Value (R,W) √√√√√√√√√√
Occupied Cool Setpoint AV 43 Present_Value (R,W) √√√√√√√√√√