BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS
63-4523—02 18
Standard Object Types Supported
Table 6. Standard Object Types Supported
a
The following AV’s are defined as read only. When Out_of_Service properties is set to true, the Present_Value if written is not
derived from the application level of the thermostat.
Room Humidity (AV11)
PI Heating Demand (AV20)
PI Cooling Demand (AV21)
Economizer Output (AV22)
Eff Reset Humidification RH Spt (AV96)
Humidifier Output (AV101)
b
Object_Name property is writable for 1 object only :
Room_Temperature (AV7)
Proprietary Properties
Table 7. Proprietary Properties
Object Type
Supported
Objects
Dynamically
Creatable
Dynamically
Deletable
Optional
Properties
Supported
Writable Properties
Analog Input
;
Reliability Out_of_Service
Analog Value ; Reliability
Present_Value
a
Out_of_Service
a
Object_Name
b
Binary Input
;
Reliability
Active_Text
Inactive_Text
Out_of_Service
Binary Value ;
Reliability
Active_Text
Inactive_Text
Present_Value
Out_of_Service
Device ;
Max_Master
Max_Info_frames
Object_Identifier
Object_name
Max_Master
Group ; N/A N/A
Multi-state Value ;
Reliability
States_Text
Present_Value
Out_of_Service
Schedule ; Weekly_schedule
Present_Value
Weekly_Schedule
Property name ID BACnet Data type Description
Major_Version 1000 CharacterString
The version number of the BACnet communications
module. This is the hardware version number.
MS/TP_Address 1001 Unsigned Display the MAC layer address of the module
MS/TP_Baud_Rate 1002 Unsigned Display the communication baud rate of the module
Sensor_Offset 1005 REAL
Display the temperature or humidity calibration value.
The range is –5.0 deg F to 5.0 deg F for a temperature
and –15% to 15% for humidity.