Installation Guide
69-1920EFS—01 6
ENGLISH
1
0
Done Next
MCR29454
Tobegin,press and hold the s and FAN
buttons until the display changes.
Function
number
Setting
Press s or t to change settings.
Press NEXT to advance to the next function.
PressDONEtoexitandsavesettings.
Installer setup
Follow the procedure below to configure the thermostat to match the installed
heating/coolingsystem,andcustomizefeatureoperationasdesired.
Continued on next page
Setup function Settings & options (factory default in bold)
Shaded areas below apply only to TH6320U/TH6220D or as otherwise noted.
*[Othercyclerateoptions:2,4,6,7,8,10,11or12CPH]
1 System type 0 1 heat/1 cool conventional
1 1 heat/1 cool heat pump (no aux. heat)
2 Heatonly—2-wiresystems,3-wirezonevalves(Series20),and
normally open zone valves
3 Heatonlywithfan
4 Cool only
5 2 heat/1 cool heat pump (with aux. heat)
6 2 heat/2 cool conventional
7 2heat/1coolconventional
8 1 heat/2 cool conventional
9 2 heat/2 cool heat pump (no aux. heat) - TH6320U only
10 3heat/2coolheatpump(withaux.heat)-TH6320U only
2 Changeover valve
(O/B terminal)
0 Changeover valve (O/B terminal energized in cooling)
1 Changeover valve (O/B terminal energized in heating)
3 Fan control
(heating)
0 Gas or oil furnace equipment controls fan in heating
1 Electricfurnace—thermostatcontrolsfaninheating
5 Stage 1 heat cycle
rate (CPH: cycles/hour)*
5 For gas or oil furnaces of less than 90% efficiency
1 For steam or gravity systems
3 Forhotwatersystems&furnaces of over 90% efficiency
9 For electric furnaces
6 Stage 2 heat cycle
rate/Auxiliary heat
cycle rate (CPH)*
5 For gas or oil furnaces of less than 90% efficiency
1 For steam or gravity systems
3 Forhotwatersystems&furnaces of over 90% efficiency
9 For electric furnaces
7 Auxiliary heat cycle
rate (CPH)*
Only TH6320U
for 3H/2C Heat Pumps
5 For gas or oil furnaces of less than 90% efficiency
1 For steam or gravity systems
3 Forhotwatersystems&furnaces of over 90% efficiency
9 For electric furnaces
8 Emergency heat cycle
rate (CPH)*
9 For electric emergency heat
1 For steam or gravity systems
3 Forhotwatersystems&furnaces of over 90% efficiency
5 For gas or oil furnaces of less than 90% efficiency