INSTALLATION INSTRUCTIONS69-2076-01S9360A, S9361A, S9370A, S9371AIntegrated Boiler ControllersAPPLICATIONThese integrated boiler control modules provi
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS69-2076—01 10Table 5. Spark Model Specific Connectors.a Indicates optional connections bas
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS11 69-2076—01“SP_” Setpoint.“Df_” Setpoint Differential (select models).“°F_” Degrees Fahr
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS69-2076—01 12Mounting Sensor and ThermowellThe remote upper temperature sensor is installe
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS13 69-2076—01Fig. 10. Operating Sequence.IGNITIONSEQUENCE IDLEALL OUTPUTS OFFCHECK LEAKAGE
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS69-2076—01 14TROUBLESHOOTINGIMPORTANT1. The following service procedures are provided as a
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS15 69-2076—01Table 7. Error Codes.Segment Display Definition Pressure Switch failed to ope
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERSAutomation and Control SolutionsHoneywell International Inc. Honeywell Limited-Honeywell L
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS69-2076—01 2Fig. 1. S936X Integrated Boiler Controller, dimensions in in. (mm).Electrical
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS3 69-2076—01Table 1. Recommended Ignition Cables.Transformer Requirement:Add current ratin
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS69-2076—01 4WARNINGFire or Explosion Hazard.Can cause severe injury, death or property dam
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS5 69-2076—01Fig. 3. Align module with slots in control box.Wire the SystemWARNINGElectrica
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS69-2076—01 6NOTE: Cable length must be 36 in. (0.9 m) or less. The cable must not be in co
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS7 69-2076—01Fig. 4. Spark Ignition Wiring (S936X).M24216CIRCULATORSPARKIGNITERFLAMESENSEIN
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS69-2076—01 8Fig. 5. Hot Surface Ignition Wiring (S937X).Common ConnectorsSENSOR 1SENSOR 2G
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS9 69-2076—01a Indicates optional connection based on configuration.HSI Model Specific Conn