PRODUCT DATA62- 3061® U.S. Registered TrademarkCopyright © 2001 Honeywell • All Rights Reserved BraukmannF74C Reverse Rinsing Filter; MV876 Automati
62-3061 10F74C REPLACEMENT PARTS LIST (SEE FIG. 16).Table 4. Parts and Accessories for F74C.Fig. 16. F74C Exploded View. parts are keyed to F74C Repla
11 62-3061
62-3061 G.R. 3-01 www.honeywell.comHome and Building Control Home and Building ControlHoneywell Honeywell Limited-Honeywell Limitée1985 Douglas D
F74C REVERSE RINSING FILTER; MV876 AUTOMATIC-BACKWASH CONTROLS62-3061 2ORDERING INFORMATIONWhen purchasing replacement and modernization products from
F74C REVERSE RINSING FILTER; MV876 AUTOMATIC-BACKWASH CONTROLS3 62-3061Operating Pressure Drop Versus Flow:See Fig. 2.Maximum recommended: 3 psi to 7
F74C REVERSE RINSING FILTER; MV876 AUTOMATIC-BACKWASH CONTROLS62-3061 4PLANNING THE INSTALLATIONThe F74C should be sized based on the required flow ra
F74C REVERSE RINSING FILTER; MV876 AUTOMATIC-BACKWASH CONTROLS5 62-3061INSTALLATIONWhen Installing this product...1.Read these instructions carefully.
F74C REVERSE RINSING FILTER; MV876 AUTOMATIC-BACKWASH CONTROLS62-3061 6Fig. 10. Final position of MV876 and F74C.As the F74C operates, screens become
F74C REVERSE RINSING FILTER; MV876 AUTOMATIC-BACKWASH CONTROLS7 62-3061Fig. 11. Removing the MV876 cover.Fig. 12. Installing batteries in the MV876.Fi
F74C REVERSE RINSING FILTER; MV876 AUTOMATIC-BACKWASH CONTROLS62-3061 8OPERATIONThe F74C Water Filter removes sediment and debris from the water using
F74C REVERSE RINSING FILTER; MV876 AUTOMATIC-BACKWASH CONTROLS9 62-3061Fig. 15. Water flow through the F74C.SCREENBACKWASHIMPELLERa. F74C DURING NORMA