Honeywell FocusPRO TH5000 Series User Manual Page 5

  • Download
  • Add to my manuals
  • Print
  • Page
    / 24
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 4
FocusPRO
®
TH5000 Series
5 69-1922EFS—01
ENGLISH
M29386
Wiring
Wiring guide heat pump systems
Shaded areas below apply only to TH5320U/TH5220D or as otherwise noted.
Thermostat mounting
Align the 4 tabs on the wallplate with
slotsonthebackofthethermostat,
then push gently until the thermostat
snaps in place.
Push excess wire back into
the wall opening.
Plug wall opening with
non-flammable insulation.
RcYGRC
M29381
1H/1C Heat
Pump System
Rc Power [1]
R [R+Rc joined by jumper]
Y Compressor contactor
C 24VACcommon[3]
O/B Changeover valve [7]
G Fan relay
2H/1C Heat
Pump System
(TH5220D only) [8]
Rc Power [1]
R [R+Rc joined by jumper]
Y Compressor contactor
C 24VACcommon[3]
O/B Changeover valve [7]
G Fan relay
Aux Auxiliary heat relay [12]
E Emergency heat relay [12]
L Sends output when set to Em. Heat [11]
2H/1C Heat
Pump System
(TH5320U only) [8]
Rc Power [1]
R [R+Rc joined by jumper]
Y Compressor contactor
C 24VACcommon[3]
O/B Changeover valve [7]
G Fan relay
Aux/E Auxiliary/Emergency heat relay
L Sends output when set to Em. Heat [11]
2H/2C Heat
Pump System
(TH5320U only) [9]
Rc Power [1]
R [R+Rc joined by jumper]
Y Compressor contactor (stage 1)
C 24VACcommon[3]
O/B Changeover valve[7]
G Fan relay
Y2 Compressor contactor (stage 2)
L Sends output when set to Em. Heat [11]
3H/2C Heat
Pump System
(TH5320U only) [10]
Rc Power [1]
R [R+Rc joined by jumper]
Y Compressor contactor (stage 1)
C 24VACcommon[3]
O/B Changeover valve [7]
G Fan relay
Aux/E Auxiliary/Emergency heat relay
Y2 Compressor contactor (stage 2)
L Sends output when set to Em. Heat [11]
See [notes] on page 4.
RcYGAuxELRC
M29382
RcYGAux
E
LRC
M29383
RcYGY2LRC
M29384
RcYGAux
E
LRC
Y2
M29385
Page view 4