Fire Alarm Control PanelMS-9200UDLSMS-9200UDLSEPN: 52750:A ECN 05-680IMPORTANT! The SLC Manual Document #51309 must be referenced in addit
10 MS-9200UDLS PN 52750:A 11/04/05PS2 Keyboard Interface DACT Phone Line Jacks(Nonpower-Limited)DB9FResettable Power - 24 VDC filtered, power-lim
Programming Master Programming Level100 MS-9200UDLS PN 52750:A 11/04/053.6.9.2.4.2 Terminal 1 and Terminal 2Service Terminal #1 is generally des
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 1013.6.9.2.4.3 Ring CountThe ring count designates the number of rings allow
Programming Master Programming Level102 MS-9200UDLS PN 52750:A 11/04/053.6.9.2.5.2 Backup ReportingThe DACT can be programmed to transmit report
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 1033.6.9.2.6.1 Central Station Primary and Secondary Phone NumbersPressing 1
Programming Master Programming Level104 MS-9200UDLS PN 52750:A 11/04/05Test Time IntervalPressing 1 while viewing Primary/Secondary Screen #1 wil
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 10524 Hour Test TimePressing 3 while viewing Primary/Secondary Screen #1 will
Programming Master Programming Level106 MS-9200UDLS PN 52750:A 11/04/05Communication FormatPressing 1 while viewing Primary/Secondary Screen #3 w
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 107The Communication Format is determined by the type of receiver that the DA
Programming Master Programming Level108 MS-9200UDLS PN 52750:A 11/04/05 3+1, 4+1 Express and 4+1 StandardThe information shown in Table 3.2 is a
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 109MON-USER-DEF-16 0 0PROCMON AR 0 0MON-USER-DEF-17 0 0not used 0 0not used 0
MS-9200UDLS PN 52750:A 11/04/05 11Peripheral Devices and Their Documents:LCD-80F Doc. #51338AFM-16AF Doc. #15210LDM-32F Doc. #50055AFM-16ATF &
Programming Master Programming Level110 MS-9200UDLS PN 52750:A 11/04/054+2 Standard, 4+2 Express, 3 + 1, 4 + 1 and 4+2 Expanded FormatsThe inform
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 111MON-USER-DEF-16 00 00PROCMON AR 00 00MON-USER-DEF-17 00 00not used 00 00no
Programming Master Programming Level112 MS-9200UDLS PN 52750:A 11/04/05Ademco Contact ID FormatThe information shown in Table 3.4 is automatical
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 113MON-USER-DEF-16 000PROCMON AR 000MON-USER-DEF-17 000not used 000not used 0
Programming Master Programming Level114 MS-9200UDLS PN 52750:A 11/04/05Report StylePressing 3 while viewing Central Station Screen #2 will cause
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 1153.6.9.3 Printer/PCA Printer or a PC can be connected to the control panel
Programming Master Programming Level116 MS-9200UDLS PN 52750:A 11/04/053.6.10 Password Change The factory set passwords, which have been program
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 1173.6.11 Clear ProgramPressing 2 while viewing Programming Screen #4, will
Programming Master Programming Level118 MS-9200UDLS PN 52750:A 11/04/053.6.12 Program CheckThe Program Check feature allows the programmer to vi
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 119Pressing 2 while viewing the Program Check screen will display a screen si
Product Description Features and Options12 MS-9200UDLS PN 52750:A 11/04/05SECTION 1 Product DescriptionThe Fire-LiteMS-9200UDLS is a combination
Programming Maintenance Programming Level120 MS-9200UDLS PN 52750:A 11/04/053.7 Maintenance Programming LevelTo access Maintenance Programming m
Maintenance Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 1213.7.1 Disable PointPressing 1 for Point Program, while viewing Maint
Programming Maintenance Programming Level122 MS-9200UDLS PN 52750:A 11/04/053.7.2 HistoryPressing 2 while viewing Maintenance Screen #1 will cau
Maintenance Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 1233.7.3 Program CheckPressing 3 while viewing Maintenance Screen #1 wi
Programming Maintenance Programming Level124 MS-9200UDLS PN 52750:A 11/04/05Pressing 3 while viewing Program Check screen will cause a screen sim
Maintenance Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 125Pressing 1 while viewing the System Screen will cause the following s
Programming Maintenance Programming Level126 MS-9200UDLS PN 52750:A 11/04/053.7.6 Zone SetupPressing 3 while viewing Maintenance Screen #2 will
Maintenance Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 127Pressing 3 while viewing Zone Setup screen will display the following
Operating Instructions Panel Control Buttons128 MS-9200UDLS PN 52750:A 11/04/05SECTION 4 Operating Instructions4.1 Panel Control Buttons4.1.1 A
LED Indicators Operating InstructionsMS-9200UDLS PN 52750:A 11/04/05 1294.2 LED IndicatorsThe nine LED indicators, which are located on the fron
Specifications Product DescriptionMS-9200UDLS PN 52750:A 11/04/05 13• Telephone Line Active LEDs • Communication Confirmation (Kissoff) LED• Touc
Operating Instructions Normal Operation130 MS-9200UDLS PN 52750:A 11/04/054.3 Normal OperationWith no alarms or troubles in the system, the disp
Trouble Operation Operating InstructionsMS-9200UDLS PN 52750:A 11/04/05 131Addressable Smoke Detectors, Monitor Modules and Control ModulesFor ad
Operating Instructions Alarm Operation132 MS-9200UDLS PN 52750:A 11/04/05Pressing the Acknowledge/Step or Alarm Silence key will cause the pulsin
Supervisory Operation Operating InstructionsMS-9200UDLS PN 52750:A 11/04/05 133• Second line in display: <ADJ>; refers to the user program
Operating Instructions Process Monitor Operation134 MS-9200UDLS PN 52750:A 11/04/054.7 Process Monitor OperationProcess Monitor operation will i
Programmed Zone Operation Operating InstructionsMS-9200UDLS PN 52750:A 11/04/05 1354.11 Programmed Zone OperationEach addressable detector and m
Operating Instructions Synchronized NAC Operation136 MS-9200UDLS PN 52750:A 11/04/054.16 Synchronized NAC OperationSynchronization is a panel fe
Positive Alarm Sequence Operating InstructionsMS-9200UDLS PN 52750:A 11/04/05 1374.19 Positive Alarm SequencePAS (Positive Alarm Sequence) optio
Operating Instructions Special System Timers138 MS-9200UDLS PN 52750:A 11/04/054.20 Special System Timers4.20.1 Silence Inhibit TimerThis optio
Walktest Operating InstructionsMS-9200UDLS PN 52750:A 11/04/05 1394.20.5 Alarm Verification (None or One Minute)If alarm verification is selecte
Product Description Specifications14 MS-9200UDLS PN 52750:A 11/04/05Battery (Lead Acid Only) - J9Maximum Charging Circuit: Normal Flat Charge - 2
Operating Instructions Read Status140 MS-9200UDLS PN 52750:A 11/04/054.22 Read StatusRead Status functions do not require a password. The contr
Read Status Operating InstructionsMS-9200UDLS PN 52750:A 11/04/05 1414.22.1 System Point Pressing 1 while viewing Read Status Screen #1 will cau
Operating Instructions Read Status142 MS-9200UDLS PN 52750:A 11/04/05Pressing the down arrow key, while viewing the screen shown above, will allo
Read Status Operating InstructionsMS-9200UDLS PN 52750:A 11/04/05 1434.22.3 PowerPressing 3 while viewing Read Status Screen #1 will cause the f
Operating Instructions Read Status144 MS-9200UDLS PN 52750:A 11/04/054.22.4 Trouble ReminderPressing 1 while viewing Read Status Screen #2 will
Read Status Operating InstructionsMS-9200UDLS PN 52750:A 11/04/05 1454.22.6 NACPressing 3 while viewing Read Status Screen #2 will display the f
Operating Instructions Read Status146 MS-9200UDLS PN 52750:A 11/04/054.22.8 Program CheckPressing 2 while viewing Read Status Screen #3 will cau
Read Status Operating InstructionsMS-9200UDLS PN 52750:A 11/04/05 1474.22.10 AnnunciatorsPressing 1 while viewing Read Status Screen #4 will dis
Operating Instructions Read Status148 MS-9200UDLS PN 52750:A 11/04/054.22.12 Central StationPressing 3 while viewing Read Status Screen #4 will
Read Status Operating InstructionsMS-9200UDLS PN 52750:A 11/04/05 1494.22.13 Service TerminalPressing 1 while viewing Read Status Screen #5 will
Specifications Product DescriptionMS-9200UDLS PN 52750:A 11/04/05 15EIA-485 (TERM) or EIA-232 (ACS) - TB8EIA-485 Terminal Mode annunciator connec
Operating Instructions Read Status150 MS-9200UDLS PN 52750:A 11/04/054.22.15 PrintTo print program data or control panel status, press 3 while v
Read Status Operating InstructionsMS-9200UDLS PN 52750:A 11/04/05 151Drift CompensationDrift compensation uses software algorithms that identify
Operating Instructions Read Status152 MS-9200UDLS PN 52750:A 11/04/054.22.16 Time-DateThe operator can view the daylight savings time and the mo
Read Status Central Station CommunicationsMS-9200UDLS PN 52750:A 11/04/05 153SECTION 5 Central Station CommunicationsThe control panel transmits
Central Station Communications Read Status154 MS-9200UDLS PN 52750:A 11/04/05The control panel is capable of reporting detailed messages dependin
Read Status Central Station CommunicationsMS-9200UDLS PN 52750:A 11/04/05 155Note: For Expanded Reporting, the control panel automatically adds t
Central Station Communications Transmittal Priorities156 MS-9200UDLS PN 52750:A 11/04/055.1 Transmittal PrioritiesThe integral communicator tran
Transmittal Priorities Central Station CommunicationsMS-9200UDLS PN 52750:A 11/04/05 1579200UDLS.1. With 685-8 Line Card with Rev. 4.4d software2
Remote Site Upload/Download Downloading Program158 MS-9200UDLS PN 52750:A 11/04/05SECTION 6 Remote Site Upload/DownloadThe control panel may be p
Downloading Program Remote Site Upload/DownloadMS-9200UDLS PN 52750:A 11/04/05 159Anytime a download with callback is initiated, the first thing
Product Description Controls and Indicators16 MS-9200UDLS PN 52750:A 11/04/051.3 Controls and IndicatorsLCD Display The FACP uses an 80-characte
Remote Site Upload/Download Downloading Program160 MS-9200UDLS PN 52750:A 11/04/05Panel Identification Number The panel identification number is
Downloading Initiated at a Service Terminal Remote Site Upload/DownloadMS-9200UDLS PN 52750:A 11/04/05 1616.2 Downloading Initiated at a Service
Remote Site Upload/Download Uploading Initiated at a Service Terminal162 MS-9200UDLS PN 52750:A 11/04/056.3 Uploading Initiated at a Service Ter
Overview Power Supply CalculationsMS-9200UDLS PN 52750:A 11/04/05 163SECTION 7 Power Supply Calculations7.1 OverviewThis section contains instru
Power Supply Calculations Calculating the System Current Draw164 MS-9200UDLS PN 52750:A 11/04/057.3 Calculating the System Current Draw7.3.1 Ov
Calculating the System Current Draw Power Supply CalculationsMS-9200UDLS PN 52750:A 11/04/05 165Table 7.3 contains columns for calculating curre
Power Supply Calculations Calculating the Battery Size166 MS-9200UDLS PN 52750:A 11/04/057.4 Calculating the Battery SizeUse Table 7.4 to calcu
Correlations Software ZonesMS-9200UDLS PN 52750:A 11/04/05 167APPENDIX A Software ZonesA.1 CorrelationsSetup and configuration of an addressab
Software Zones Correlations168 MS-9200UDLS PN 52750:A 11/04/05Correlation of Input and Output ZonesThe zone correlations which are shown graphica
Correlations Software ZonesMS-9200UDLS PN 52750:A 11/04/05 169Table A.1 Detector Programming Sheet ExampleDETECTOR ZONE ASSIGNMENTAddress Device
Circuits Product DescriptionMS-9200UDLS PN 52750:A 11/04/05 171.4 CircuitsSLC Communication LoopOne SLC loop is provided standard on the FACP ma
Software Zones Correlations170 MS-9200UDLS PN 52750:A 11/04/05Table A.2 Module Programming Sheet ExampleMONITOR/CONTROL MODULE ZONE ASSIGNMENTAd
Correlations Software ZonesMS-9200UDLS PN 52750:A 11/04/05 171Table A.3 Blank Detector Programming Sheet - 1 of 2DETECTOR ZONE ASSIGNMENTAddress
Software Zones Correlations172 MS-9200UDLS PN 52750:A 11/04/05Table A.4 Blank Module Programming Sheet - 1 of 2MONITOR/CONTROL MODULE ZONE ASSIG
Correlations Default ProgrammingMS-9200UDLS PN 52750:A 11/04/05 173APPENDIX B Default ProgrammingThe following table provides a list of the pro
NFPA Standard-Specific Requirements Correlations174 MS-9200UDLS PN 52750:A 11/04/05APPENDIX C NFPA Standard-Specific RequirementsThe MS-9200UDL
Correlations NFPA Standard-Specific RequirementsMS-9200UDLS PN 52750:A 11/04/05 175NFPA 72 Auxiliary Fire Alarm SystemAll connections are power-l
NFPA Standard-Specific Requirements Correlations176 MS-9200UDLS PN 52750:A 11/04/05NFPA 72 Remote Station Protective Signaling SystemNotes:1. Cut
Correlations NFPA Standard-Specific RequirementsMS-9200UDLS PN 52750:A 11/04/05 177NFPA 72 Proprietary Protective Signaling Systems Figure C.3 Pr
Wire Requirements Correlations178 MS-9200UDLS PN 52750:A 11/04/05APPENDIX D Wire RequirementsT-tapping of the SLC loop wiring is allowed for 2-
Control Module Operation HVAC ControlMS-9200UDLS PN 52750:A 11/04/05 179APPENDIX E HVAC ControlThe FACP can be programmed to shut down a buildi
Product Description Components18 MS-9200UDLS PN 52750:A 11/04/051.6 ComponentsMain Circuit BoardThe main circuit board contains the system’s CPU
HVAC Control Monitor Module Operation180 MS-9200UDLS PN 52750:A 11/04/05E.2.2 HVAC OVRRIDEThe HVAC OVRRIDE type code can be assigned to any addr
MS-9200UDLS PN 52750:A 11/04/05 181IndexNumerics24 Hour Test Time 105300 Series
182 MS-9200UDLS PN 52750:A 11/04/05IndexClass A 32Class B 32NAC wiring 33CLIP modesee also Classic Loop Interface Protocol 79Clock Format 83Coded
MS-9200UDLS PN 52750:A 11/04/05 183IndexGgeneral alarm zone 64see also zone Z00
184 MS-9200UDLS PN 52750:A 11/04/05Indexnonpower-limitedrelay connections 32Nonresettable Power 17current 14, 31nonsilenceablewaterflow 78, 93Norm
MS-9200UDLS PN 52750:A 11/04/05 185Indexannunciators 147, 148exiting 43history 1
186 MS-9200UDLS PN 52750:A 11/04/05IndexTelephone CompanyRights and Warnings 25telephone line 36Terminal 100, 101Test Time Interval 104, 105Time a
Limited WarrantyThe manufacturer warrants products manufactured by it to be free fromdefects in materials and workmanship for eighteen (18) months fro
World HeadquartersOne Fire-Lite Place, Northford, CT 06472-1653 USA203-484-7161 • Fax 203-484-7118www.firelite.com©2005 by Honeywell International I
Components Product DescriptionMS-9200UDLS PN 52750:A 11/04/05 191.6.2 Intelligent Addressable Modules: Newer SeriesThe newer series of Control M
PrecauLarge.PMD 01/10/2005An automatic fire alarm system–typically made up of smokedetectors, heat detectors, manual pull stations, audible warn-in
Product Description Optional Modules20 MS-9200UDLS PN 52750:A 11/04/051.7 Optional ModulesThe MS-9200UDLS main circuit board includes option mod
Accessories Product DescriptionMS-9200UDLS PN 52750:A 11/04/05 211.8.3 Battery BoxBB-26The BB-26 battery box may be used to house up to two 26 A
Product Description Accessories22 MS-9200UDLS PN 52750:A 11/04/051.8.5 AnnunciatorsACS Series LED Zone Type AnnunciatorsThe ACS Series Annunciat
Getting Started Product DescriptionMS-9200UDLS PN 52750:A 11/04/05 23LCD-80F Remote Fire Annunciator The LCD-80F annunciator is a compact 80-char
Product Description Telephone Requirements and Warnings24 MS-9200UDLS PN 52750:A 11/04/051.10 Telephone Requirements and Warnings1.10.1Telephone
Telephone Requirements and Warnings Product DescriptionMS-9200UDLS PN 52750:A 11/04/05 251.10.3Telephone Company Rights and WarningsThe telephone
Product Description Telephone Requirements and Warnings26 MS-9200UDLS PN 52750:A 11/04/051.10.4For Canadian ApplicationsThe following is excerpte
Mounting Backbox InstallationMS-9200UDLS PN 52750:A 11/04/05 27SECTION 2 InstallationThe cabinet may be either semi-flush or surface mounted. Th
Installation Mounting Transformer28 MS-9200UDLS PN 52750:A 11/04/052.2 Mounting TransformerOne XRM-24(E) transformer is supplied standard with t
Mounting Transformer InstallationMS-9200UDLS PN 52750:A 11/04/05 29Figure 2.3 MS-9200UDLS Cabinet Mounting9050udencl.cdrSemi-Flush MountingDo not
PrecauLarge.PMD 01/10/2005WARNING - Several different sources of power can be con-nected to the fire alarm control panel. Disconnect all sourcesof
Installation Mounting Transformer30 MS-9200UDLS PN 52750:A 11/04/05Figure 2.4 MS-9200UDLS Cabinet Dimensions9050udcab.cdr
Power InstallationMS-9200UDLS PN 52750:A 11/04/05 312.3 PowerWARNING: Several different sources of power can be connected to this panel. Discon
Installation Relays32 MS-9200UDLS PN 52750:A 11/04/052.4 RelaysThe FACP provides two programmable Form-C relays and one fixed fail-safe Form-C t
Notification Appliance Circuits InstallationMS-9200UDLS PN 52750:A 11/04/05 332.5.1 Configuring NACsThe Notification Appliance Circuits on the m
Installation Remote Synchronization Output34 MS-9200UDLS PN 52750:A 11/04/052.5.3 Style Z (Class A) NAC Wiring 2.6 Remote Synchronization Outpu
UL Power-limited Wiring Requirements InstallationMS-9200UDLS PN 52750:A 11/04/05 352.7 UL Power-limited Wiring RequirementsPower-limited and non
Installation Digital Communicator36 MS-9200UDLS PN 52750:A 11/04/052.8 Digital CommunicatorTwo independent telephone lines can be connected to t
Optional Module Installation InstallationMS-9200UDLS PN 52750:A 11/04/05 372.9 Optional Module InstallationWARNING! Disconnect all sources of p
Installation Optional Module Installation38 MS-9200UDLS PN 52750:A 11/04/052.9.1 4XTMF Transmitter Module InstallationThe 4XTMF provides a super
Optional Module Installation InstallationMS-9200UDLS PN 52750:A 11/04/05 39The following steps must be followed when installing the 4XTMF module:
4 MS-9200UDLS PN 52750:A 11/04/05Notes
Installation Optional Module Installation40 MS-9200UDLS PN 52750:A 11/04/052.9.2 Printer/PC A serial printer or a PC (personal computer) may be
Optional Module Installation InstallationMS-9200UDLS PN 52750:A 11/04/05 412.9.3 Digital Communicator and Annunciators2.9.3.1 ACM-8RF Relay Con
Programming Programming Data Entry42 MS-9200UDLS PN 52750:A 11/04/05SECTION 3 Programming 3.1 Programming Data EntryProgramming can be accomplis
User Programming ProgrammingMS-9200UDLS PN 52750:A 11/04/05 433.2 User ProgrammingThe MS-9200UDLS is completely field programmable and requires
Programming Initial Power-up44 MS-9200UDLS PN 52750:A 11/04/05User Programming LevelsThere are two user programming levels:• User Master Program
Programming and Passwords ProgrammingMS-9200UDLS PN 52750:A 11/04/05 45To access user Programming mode, press the Enter or Mode key. The LCD wil
Programming Master Programming Level46 MS-9200UDLS PN 52750:A 11/04/053.6 Master Programming LevelWhen the Master Program Level password is ente
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 473.6.1 AutoprogramPressing 1 while viewing Programming Screen #1, will sele
Programming Master Programming Level48 MS-9200UDLS PN 52750:A 11/04/053.6.2 Point ProgramThe Point Program option allows the programmer to add a
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 49When the type has been selected, the following screen will be displayed: Th
MS-9200UDLS P/N: 52750:A 11/04/05
Programming Master Programming Level50 MS-9200UDLS PN 52750:A 11/04/05If no detectors have been installed on the loop, the following will be disp
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 51The following examples show the editing of a photoelectric smoke detector w
Programming Master Programming Level52 MS-9200UDLS PN 52750:A 11/04/05TypeTo select the type of detector being programmed, press the 2 key while
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 53PASThe PAS (Positive Alarm Sequence) option will program the detector to de
Programming Master Programming Level54 MS-9200UDLS PN 52750:A 11/04/05With the preceding program settings, when the detector with address 005 is
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 55Pressing 1 while viewing the Noun/Adjective Screen will cause the following
Programming Master Programming Level56 MS-9200UDLS PN 52750:A 11/04/05Pressing 2 while viewing the Noun/Adjective Screen will cause the following
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 57Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screen
Programming Master Programming Level58 MS-9200UDLS PN 52750:A 11/04/05As an example, the user could quickly enter ‘FLR_3_ROOM_305’ as follows:1.
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 59Pressing 1 for Control Module or 2 for Monitor Module will cause the follow
Table of Contents6
Programming Master Programming Level60 MS-9200UDLS PN 52750:A 11/04/05A flashing cursor will appear in the position of the first asterisk to the
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 61If the selected address corresponds to a control module, a screen displayin
Programming Master Programming Level62 MS-9200UDLS PN 52750:A 11/04/05Enable/Disable ModuleTo Enable or Disable the monitor module, press the 1 k
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 63Monitor module type selection will affect the function of the point as foll
Programming Master Programming Level64 MS-9200UDLS PN 52750:A 11/04/05Pre-signalTo enable the Pre-signal feature, press 1 while viewing Edit Moni
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 65Pressing 1 while viewing the Noun/Adjective Screen will cause the following
Programming Master Programming Level66 MS-9200UDLS PN 52750:A 11/04/05Pressing 2 while viewing the Noun/Adjective Screen will cause the following
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 67DescriptionThe Description selection allows the programmer to enter additio
Programming Master Programming Level68 MS-9200UDLS PN 52750:A 11/04/05As an example, the user could quickly enter ‘FLR_3_ROOM 305’ as follows:1.
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 69To change the programming for the displayed module, press the keyboard down
MS-9200UDLS P/N: 52750:A 11/04/05
Programming Master Programming Level70 MS-9200UDLS PN 52750:A 11/04/05TypeTo select the type of control module being programmed, press the 2 key
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 71SilenceableThe Silenceable selection allows the programmer to select whethe
Programming Master Programming Level72 MS-9200UDLS PN 52750:A 11/04/05Pressing 1 while viewing the Noun/Adjective Screen will cause the following
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 73Pressing 2 while viewing the Noun/Adjective Screen will cause the following
Programming Master Programming Level74 MS-9200UDLS PN 52750:A 11/04/05DescriptionThe Description selection allows the programmer to enter additio
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 753.6.3 Zone SetupPressing 3 while viewing Programming Screen #2 will access
Programming Master Programming Level76 MS-9200UDLS PN 52750:A 11/04/053.6.3.2 DisablePressing 2 for Disable, while viewing Zone Setup Screen #1,
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 773.6.3.4 Zones InstalledPressing 1 for Zones Installed, while viewing Zone
Programming Master Programming Level78 MS-9200UDLS PN 52750:A 11/04/053.6.3.7 Zone TypeZone Types must be programmed only if a DACT, programmed
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 793.6.3.8 Zones AvailablePressing 2 while viewing Zone Setup Screen #3 will
Table of Contents8
Programming Master Programming Level80 MS-9200UDLS PN 52750:A 11/04/05detectors and 99 control/monitor modules. Newer devices can be set to addr
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 813.6.5.1 Trouble ReminderThe Trouble Reminder features causes the control p
Programming Master Programming Level82 MS-9200UDLS PN 52750:A 11/04/05to view the second screen. Enter up to 20 characters in the second screen
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 833.6.5.3.2 DateTo change the date, press 2 while viewing the Time-Date Scre
Programming Master Programming Level84 MS-9200UDLS PN 52750:A 11/04/05Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-sc
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 853.6.5.4.2 Pre-signal DelayThe factory default setting for Pre-signal delay
Programming Master Programming Level86 MS-9200UDLS PN 52750:A 11/04/053.6.5.4.4 AC Loss DelayThe reporting of a loss of AC power to a central st
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 87The following screens will be displayed for each selection:3.6.5.5.1 Enabl
Programming Master Programming Level88 MS-9200UDLS PN 52750:A 11/04/053.6.5.5.2 TypeThe main circuit board NAC type can be programmed by pressin
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 893.6.5.5.4 Auto SilenceThe Auto Silence feature, when enabled, automaticall
MS-9200UDLS PN 52750:A 11/04/05 9It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and b
Programming Master Programming Level90 MS-9200UDLS PN 52750:A 11/04/05The programmer can select the notification appliance output by pressing the
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 913.6.5.5.6 ZoneA maximum of five zones can be programmed to each main circu
Programming Master Programming Level92 MS-9200UDLS PN 52750:A 11/04/053.6.5.6 RelaysPressing 3 while viewing System Setup Screen #2 will allow t
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 933.6.5.7 Canadian OptionPressing 1 while viewing System Setup Screen #3 wil
Programming Master Programming Level94 MS-9200UDLS PN 52750:A 11/04/053.6.7 HistoryThe History option allows an authorized user to view or erase
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 953.6.8 WalktestWalktest allows an individual to test the fire alarm system
Programming Master Programming Level96 MS-9200UDLS PN 52750:A 11/04/053.6.9 Option ModulesOptions available for the MS-9200UDLS include ACS Ser
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 97If an ACS annunciator is installed, press 1 while viewing Annunciator Scree
Programming Master Programming Level98 MS-9200UDLS PN 52750:A 11/04/053.6.9.2.2 Primary PhonePress 2 while viewing On Board DACT Screen #1 to pr
Master Programming Level ProgrammingMS-9200UDLS PN 52750:A 11/04/05 993.6.9.2.4 Service TerminalThe MS-9200UDLS can be programmed remotely from