Honeywell VISTA-20P User Manual

Browse online or download User Manual for Safety Honeywell VISTA-20P. Honeywell VISTA-20P User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 80
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
ADEMCO VISTA SERIES
VISTA-20P / VISTA-20PSIA
VISTA-15P / VISTA-15PSIA
Security Systems
Installation and Setup Guide
K5305-1V5 10/04 Rev. A
Page view 0
1 2 ... 80

Summary of Contents

Page 1 - ADEMCO VISTA SERIES

ADEMCO VISTA SERIES VISTA-20P / VISTA-20PSIA VISTA-15P / VISTA-15PSIA Security Systems Installation and Setup Guide K5305-1V5

Page 2 - APPLIANCES

Sounder (Bell) Connections Basic Connections spkr_conn-001-V0ALARM OUTPUT10.5 - 13.5 VDC2A MAX.34 Make sounder connections to alarm output terminals

Page 3 - Table Of Contents

Keypad Notes ARMEDREADY1OFF4MAX7INSTANTREADY2AWAY5TEST8CODE03STAY6BYPASS9CHIME# Set device addresses. Refer to the instructions included with the de

Page 4

Hardwire Zones and Zone Expansion Hardwire Zones zones-001-V0HILO Normally Open Zones/ N.O. EOLR Zones 1. Connect open circuit devices in parallel

Page 5 - Capabilities and Functions

Smoke Detector Notes •••• Fire Verification (zone type 16): The control panel will “verify” a fire alarm by resetting the smoke detectors after the

Page 6 - Compatible Devices

BRNGRNBLK(–) GROUNDRED(+) 12VDCYEL4321ZONESABC DFGHDIP SWITCHFOR SETTING ADDRESSAND ZONE "A" RESPONSETAMPER JUMPER POSITION4229 IN CABIN

Page 7 - SECTION 2

Installing a 5800TM Module • Use this module only if you are using one or more wireless bi-directional keypads or keyfobs with a wireless Receiver

Page 8

Installing a Keyswitch Keyswitch Connections GREENRED 1. Connect the 4146 keyswitch's normally open momentary switch to a zone’s (2-8) termin

Page 9 - CONTROL BOARD

Connecting Relay Modules, Powerline Carrier Devices and Output Triggers 4204/4229 Relay Modules UL For UL installation requirements, refer to the

Page 10 - Use a UL Listed

On-Board Triggers Connect field wiring to the desired trigger pin on the 8-pin trigger connector centrally located above the terminal strip. • If

Page 11 - Table of Device Addresses

Phone Line/Phone Module, and Audio Alarm Verification (AAV) Connections Phone Line Connect incoming phone line and handset wiring to the main termin

Page 12 - Installation and Setup Guide

RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Cover

Page 13 - DETECTOR

Audio Alarm Verification Connections (AAV, “listen-In”) • Refer to the connection diagrams below. One diagram shows connections when a 4285/4286

Page 14 - 4229-002-V0

SECTION 3 Programming Overview About Programming • You can program the system at any time, even at the installer's premises prior to the actua

Page 15

Interactive Mode Programming (∗∗∗∗56, *57, ∗∗∗∗58, ∗∗∗∗79, ∗∗∗∗80, ∗∗∗∗81, ∗∗∗∗82) Entering Interactive Mode Press [∗] + [Interactive Mode No.] (for e

Page 16 - Installing a Keyswitch

Type 05 Trouble by Day/ Alarm by Night • Assign to a zone that contains a foil-protected door or window (such as in a store), or to a zone covering

Page 17 - 87654321

Type 23 * No Alarm Response • Can be used on a zone when an output relay action is desired, but with no accompanying alarm (e.g., lobby door access)

Page 18

SECTION 4 Data Field Programming About Data Field Programming The following pages list this control’s data fields in numerical order. Valid entries f

Page 19 - V IP MODULE

*32 Fire Alarm Sounder Timeout 0 = yes; sounder timeout after time selected in field ∗33 1 = no timeout; sounds until manually turned off This contr

Page 20

*47 Phone System Select If Central Station Receiver is not on WATS line: 0 = Pulse Dial; 1 = Tone Dial If Central Station Receiver is on WATS line

Page 21 - Programming Overview

System Status Report Codes Zone report codes are programmed using interactive ✱56 or ✱58 Zone Programming modes, while system status (non-alarm) code

Page 22 - Zone Type Definitions

*69 Recent Closing Report V20PSIA/V15PSIA only Always enabled. Field does not apply to other controls. Similar to the Exit Error condition describe

Page 23

Table Of Contents Features and Installation Highlights...

Page 24

*87 Misc. Fault Delay Time 0 = 15 secs 4 = 90 secs 8 = 4 min #+12 = 8 min 1 = 30 secs 5 = 2 min 9 = 5 min #+13 = 10 min 2 = 45 secs 6 = 2-1/2 m

Page 25 - Data Field Programming

*93 No. of Reports In Armed Period per Zone (Swinger Suppression) 0 = unlimited number of reports 1 = 1 report pair per zone per armed period 2 = 2 re

Page 26

*161 Pager 1 Characters Enter up to 16 characters. Up to 16 optional characters may be sent as a prefix to the 7-digit system status code sent to Pag

Page 27

Configurable Zone Type Fields • The system allows you to define custom zone types (VISTA-20P supports 4 [types 90-93]; VISTA-15P supports 2 [types 90,

Page 28

Configurable Zone Type Charts ENTRY 1 ENTRY 2 Response when system disarmed and zone is: Intact EOL RF zone normal Open RF zone N/A Shorted RF zn o

Page 29 - V20PSIA/V15PSIA only

Touch Screen Keypad (AUI) Enable The system supports up to two touch screen style keypads (e.g., Symphony Advanced User Interface (AUI), and 6270 Tou

Page 30

Installation and Setup Guide 4-12

Page 31

SECTION 5 Menu Mode Programming Zones and Partitions Each protection zone needs to be programmed with various attributes using *56 Zone Programming

Page 32

Enter Zn Num. (00 = Quit) 10 Zone Number VISTA-20P: wired 01-08 (and 09-48†); wireless 09-48; RF button zones 49-64 VISTA-15P: wired 01-06 (a

Page 33 - (0-9, # + 10 = 10

10 INPUT TYPE RF TRANS 3 Input Device type (In) 2 = AW (Aux wired zone) 3 = RF (supervised RF transmitter 4 = UR (unsupervised RF transmitter)

Page 34 - Zone Conditions Represented

Table Of Contents (continued) Data Field Programming ...

Page 35

Entd A022-4063 1 Rcvd A022-4064 1 If Serial or Loop Numbers do not match after activating the transmitter [∗] to continue If the serial number

Page 36

Zn ZT P RC HW: RT 01 09 1 10 EL 1 Zn ZT P RC IN: L 10 00 1 10 :RF – Summary Screen 01-64 = zone number; [∗] to contin

Page 37 - Menu Mode Programming

Entd A022-4063 Rcvd A022-4064 If Serial or Loop Numbers do not match after activating the transmitter [∗] to continue If the serial/

Page 38

XMIT TO CONFIRM PRESS ✱ TO SKIP Confirm [∗] to continue • If “Yes” was entered at the SET TO CONFIRM? prompt previously (see first prompt follo

Page 39 - ✱ TO SKIP

About Output Device Programming (*79/*80 Menu Mode) Output Devices: The VISTA-20P system supports up to 16 relays and/or Powerline Carrier devices

Page 40 - Completing Zone Programming

Start Output Device Mapping by pressing *79 while in Data Programming Mode. ∗∗∗∗79 Menu Mode ENTER OUTPUT NO. 00 = QUIT xx Device Output Numbe

Page 41 - AXXX-XXX –

*80 Menu Mode: Defining Output Functions Use this mode to program output function definitions (up to 48 functions) that provide automated control of a

Page 42 - ] to continue

“A” 01 Zn List 1 Zone List (prompt appears if zone list was selected) 01-08 = zone list; [∗] to continue Enter the desired zone list number associa

Page 43 - These transmitters

Enter Output No. R02 02 Output Number 01-16 = VISTA-20P output no.; 01-08 = VISTA-15P output no.; 17-18 = on-board triggers Enter the device outp

Page 44 - Programming Output Devices

About Function Keys (*57 Menu Mode) The system provides the ability to program each of the four keypad function keys to perform one of 12 system opera

Page 45

SECTION 1 Features and Installation Highlights This manual applies to the following Honeywell security systems: ADEMCO VISTA-20P/ADEMCO VISTA-20PSIA/

Page 46

About Descriptor Programming (*82 Menu Mode) The system lets you assign zone descriptors for protection zones, keypad panics, and RF receiver supervis

Page 47

✱ ZN 01 BACK Accept First Word 6 = save word and go to next word in this descriptor; 8 = save word and go to next zone Press [6] to accept

Page 48 - Zone List Programming

ALPHA VOCABULARY LIST (For Entering Zone Descriptors) 000 (Word Space) – A – • 001 AIR • 002 ALARM ∗∗∗∗ 004 ALLEY 005 AMBUSH • 006 AREA •

Page 49 - Programming Function Keys

Programming Installer and User Schedules The system provides schedules, which can be used to automatically control 11 types of system events at pre-de

Page 50

STOP SMTWTFS HH MMAM 0010000 Stop Time (For events 01-relay on/off; 02-user access; 03-latch key report) 01-12 = hour; 00-59 = minute; 0 = A

Page 51

SECTION 6 System Communication and Operation Panel Communication with Central Station This system accommodates several formats for reporting alarms a

Page 52 - ALPHA VOCABULARY LIST

The following table lists codes for reports sent in different formats: Code for Code for Type of 3+1/4+1 3+1/4+1 Code for Report Standard Ex

Page 53 - HH MMAM 0010000

Ademco Contact ID® The Ademco Contact ID® Reporting Format comprises the following: 4-digit or 10-digit subscriber number (depending on format selecte

Page 54 - 0=NO 1=YES X

System Security Codes The systems provides one Installer code, one System Master code, plus a set of other user codes intended for other users of the

Page 55 - Report Code Formats

Keypad Functions The following is a brief list of system commands. For detailed information concerning system functions, refer to the User's Manu

Page 56

Compatible Devices Device VISTA-20P VISTA-15P Notes Addressable Keypads 8 8 6150 Fixed-Word Keypad, 6160 Alpha Keypad, 6150V Fixed-Word Display Vo

Page 57 - Ademco Contact ID

SUMMARY OF ARMING MODES Features for Each Arming Mode Arming Mode Exit Delay Entry Delay Perimeter Armed Interior Armed AWAY Yes Yes Yes Yes STA

Page 58 - System Security Codes

Various System Trouble Displays Alpha Display Fixed Disp. Meaning ALARM CANCELED CA will appear if an exit or interior zone contained a fault duri

Page 59 - Keypad Functions

Installation and Setup Guide 6-8

Page 60 - Setting the Real-Time Clock

SECTION 7 Testing the System About Test Procedures After the installation is complete, you should perform the following tests: System Test: Checks

Page 61 - System Operation

NOTES: • All BR type units must physically be activated to clear the display. • When one button of a transmitter (RF, UR, or BR) is activated, all

Page 62

SECTION 8 Specifications & Accessories Security Control 1. Physical: 12-1/2” W x 14-1/2” H x 3” D (318mm x 368mm x 76mm) 2. Electrical: VOLTAG

Page 63 - Testing the System

2-Wire Smoke Detector: Detector Type System Sensor Model No. Photoelectric w/heat sensor, direct wire 2300TB Photoelectric, direct wire 2400 Photo

Page 64 - Go/No Go Test Mode

5800 Series Transmitter Input Loop Identification All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID c

Page 65 - Security Control

Compatible 5800 Series Transmitters Table (continued) Model Product Input Type Description 5817 Multi-Point Universal Transmitter RF Has three unique

Page 66 - System Sensor

SECTION 9 Regulatory Agency Statements RADIO FREQUENCY EMISSIONS Federal Communications Commission (FCC) Part 15 This device complies with part 15 o

Page 67 - Emergency Transmitter)

SECTION 2 Mounting and Wiring the Control Installing the Control Cabinet and PC Board Cabinet and Lock 1. Mount the control cabinet to a sturdy wa

Page 68

UL NOTICES 1. Entry Delay No. 1 and No. 2 (fields ✱35, ✱36) cannot be greater than 30 seconds for UL Residential Burglar Alarm installations, and e

Page 70 - UL NOTICES

Notes Installation and Setup Guide 9-4

Page 71

Notes 9-5

Page 72

Notes Installation and Setup Guide 9-6

Page 73

SECTION 10 Limitations and Warranty WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does no

Page 74

WARNING THE LIMITATIONS OF THIS ALARM SYSTEM (Continued) The most common cause of an alarm system not functioning when an intrusion or fire occurs

Page 75 - Limitations and Warranty

– INDEX – 1-9 1321 AC Transformer ... 1-2, 2-3, 2-11 1361X10... 2-3, 2-11, 2-12, 8-2 24-Hour Audible Alarm ... 3-3 2

Page 76

R Relay Modules... 1-2, 2-11 Relay Programming... 3-1 Report Code..4-4, 4-5, 4-6, 4-9, 5-2, 5-5, 6-1 Report

Page 77 - – INDEX –

CLASS 2 PLUG-IN TRANSFORMER16.5VAC, 25VA(e.g. ADEMCO No. 1321).(USE No. 1321CN IN CANADA)TO 110VAC UNSWITCHEDOUTLET (24HR) THIS EQUIPMENT SHOULD BE I

Page 78

ANTENNAMOUNT(2 PLACES)ANTENNA(2)SCREW(2)BLACKMOUNTINGCLIPREDMOUNTINGCLIPWHITEMOUNTINGCLIPGROUNDINGLUG(2)NOTE A COMBINATION OF THESE MOUNTING CLIPS HAS

Page 79 - SUMMARY OF CONNECTIONS

LIMITED WARRANTY Honeywell International Inc., acting through its Security & Custom Electronics business ("Seller") 165 Eileen Way, Sy

Page 80 - ÊK5305-1V5ÈŠ

AC Power, Battery, and Ground Connections 1321 Transformer TOTERMINALS1 AND 21321X10-001-V012 Connect the 1321 Transformer (1321CN in Canada) to term

Related models: VISTA-20PSIA | VISTA-15P | VISTA-15PSIA |

Comments to this Manuals

No comments