C7189U REMOTE INDOOR SENSOR
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9
http://yourhome.honeywell.com
® U.S. Registered Trademark
© 2005 Honeywell International Inc. Patents Pending.
69-1710EFS-1 M.S. Rev. 10-05
CHECKOUT
For best results, allow the sensor to absorb the air
moving through the room for a minimum of twenty
minutes before taking a resistance measurement.
1. Use an accurate thermometer (+/-1ºF[0.5ºC]) mea-
sure the temperature at the sensor location.
2. Remove one wire from one of the sensor's wiring
terminals. Use an ohmmeter to measure the resis-
tance across the sensor. Verify the sensor accu-
racy with the temperature/resistance in Table 1.
CALIBRATION
The sensor is calibrated at the factory and cannot be
recalibrated in the field.
Table 1. Sensor Resistance at Room Temperature.
Room Temperature
Ohms of
Resistance°F °C
40 4.4 22537
42 5.6 21516
44 6.7 20546
46 7.8 19626
48 8.9 18754
50 10.0 17926
52 11.1 17136
54 12.2 16387
56 13.3 15675
58 14.4 14999
60 15.6 14356
62 16.7 13743
64 17.8 13161
66 18.9 12607
68 20.0 12081
70 21.1 11578
72 22.2 11100
74 23.3 10644
76 24.4 10210
78 25.6 9795
80 26.7 9398
82 27.8 9020
84 28.9 8659
86 30.0 8315
88 31.1 7986
90 32.2 7672
92 33.3 7372
94 34.4 7086
96 35.6 6813
98 36.7 6551
100 37.8 6301
Comments to this Manuals