Honeywell T8611G User Manual Page 11

  • Download
  • Add to my manuals
  • Print
  • Page
    / 12
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 10
T8611G CHRONOTHERM
®
IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
11 69-1406—1
System on indicator
(flame=heat,
snowflake=cool) is
displayed, but no
warm or cool air is
coming from the
registers.
Heating or cooling equipment is
not operating.
Verify operation of heating or cooling equipment in self-test.
Outdoor tempera-
ture not displayed
a
Option not activated. Enter Installer Setup number 24 and set to 1. Thermostat must
have OT terminals and a C7089B1000 installed.
Outdoor
temperature
display is incorrect
a
Outdoor sensor is connected
incorrectly.
Refer to C7089B1000 Installation Instructions and check wiring
between the thermostat and sensor.
Wrong sensor. Replace sensor with C7089B1000 Sensor.
a
Select models.
Table 6. Troubleshooting Guide. (Continued)
Symptom Possible Cause Action