T8501 MICROELECTRONIC THERMOSTATS
69-0925—4 2
Fig. 1. Typical location of thermostat.
Fig. 2. Mounting the wallplate.
WIRING
All wiring must comply with local electrical codes and
ordinances. Refer to Fig. 3 and 5 for typical hookup. A
letter code is located near each terminal for identification.
CAUTION
Electrical Shock Hazard.
Can cause electrical shock and equipment
damage.
Disconnect power before wiring.
1. Loosen the terminal screws on the wallplate and
connect the system wires. See Fig. 6.
IMPORTANT
Use 18 gauge, color-coded thermostat cable for
proper wiring.
2. Securely tighten each terminal screw.
3. Push excess wire back into the hole.
4. Plug the hole with nonflammable insulation to pre-
vent drafts from affecting the thermostat.
Fig. 3. Typical hookup in heat only application.
5 FEET
[1.5 METERS]
YES
NO
NO
NO
M10106
WIRES
THROUGH WALL
WALL
MOUNTING
HOLES
MOUNTING
SCREWS
M6530A
WALL
ANCHORS
(2)
L1
(HOT)
L2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
AVAILABLE ON SELECT MODELS.
1
HEATING
RELAY OR
VALVE COIL
M4822
RO
T
O
T
C W
OUTDOOR
TEMPERATURE
SENSOR
THERMOSTAT
1
2
2