Backbox Mounting Installation
MS-2/MS-4 PN 51512:E 01/18/05 17
SECTION 2 Installation
The cabinet can be surface mounted or semi-flush mounted using the optional Trim
Ring P/N: TR-1-R. The door is removable during the installation period by opening
and lifting if off the hinges. The cabinet mounts using two key slots at the top of the
backbox and two additional 0.250” diameter holes located at the bottom.
Carefully unpack the system and check for shipping damage. Select a location for the
cabinet that is in a clean, dry, vibration-free area where extreme temperatures are not
encountered. The area should be readily accessible with sufficient room to easily install
and maintain the control panel. Locate the top of the cabinet approximately five feet
above the floor with the hinge mounting on the left.
Determine the number of conductors required for the devices to be installed and
determine the appropriate knockouts. All wiring must be in accordance with the
National and/or Local codes for fire alarm systems and power supplies.
2.1 Backbox Mounting
1. Mark and predrill holes for the top two keyhole mounting bolts
2. Install two upper fasteners in the wall with the screw heads protruding
approximately ¼”
3. Using the upper keyholes, mount the backbox over the two screws
4. Mark the lower two holes, remove the backbox from the wall and drill the
mounting holes
5. Mount the backbox, install the remaining fasteners and tighten all screws
Figure 2.1 Backbox Mounting Dimensions
Bottom
Height=15.000”
(38.10 cm)
10.375”
(26.35 cm)
0.75”(1.9 cm)
2.875” (7.3 cm)
Backbox = 14.5”
(36.8 cm)
Depth = 3.000”
(7.62 cm)
Top
9.1” (23.1 cm)
2.7”
(6.86cm)
1.125” (2.868 cm)
Pem Studs
Backbox Mounting Holes
ms2-4cab.cdr