T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
62-0255—07 16
Fig. 30. Setup - Sensors - Sensor A - 0-5V, 0-10V, OR
4-20MA - MIN and MAX Value (showing °F).
1.2.2.2.3. MIN or MAX VALUE
(Sensor A only;
0-5V, 0-10V or 4-20mA)
The minimum and maximum values display only for
Sensor A when its type is
0-5V,
0-10V or 4-20MA.
1. From the Sensor A selections, use the S and T
buttons to highlight MIN VAL or MAX VAL.
2. Press the X button to display the units.
3. Use the S and T buttons to increase/decrease the
desired value.
Sensor Ranges:
°F -60.0 to 270.0
°C -51.0 to 132.0
PSI -500 to 500
IN WC -30.0 to 30.0
% 0.0 to 100.0
PA -3000 to 3000
KPA -3000 to 3000
PPM 0 to 9990
NONE -9999 to 9999
4. Press the X button to accept the units and return to
the Sensor A selections.
Fig. 31. Setup - Sensors - Sensor A - Calibrate.
1.2.2.3. CALIBRATE (Sensor A or B)
Ensure that the wire size calibration value is within the
limits for the sensor.
For temperature sensors, see “Temperature Sensor
Calibration” on page 10.
For other sensors, see “Humidity, Pressure, and
Universal Sensor Calibration” on page 10.
1. From the Sensor A selections, use the S and T
buttons to highlight CALIBRATE.
2. Press the X button to display the calibration value.
3. Use the S and T buttons to increase/decrease the
desired calibration value.
Default: 0.0
Sensor Range Temperature: +/-10°F (+/-6°C)
Other Sensor Range: +/-10% of the Min to Max
values specified previously. See Table 3 on
page 10 for examples.
4. Press the X button to accept the value and return to
the Sensor A selections.
Fig. 32. Setup - Sensors - Sensor A - Label.
1.2.2.4. LABEL (Sensor A or B input)
For a sensor already labeled, the display positions to and
highlights that label.
1. From the Sensor A selections, use the S and T
buttons to highlight LABEL.
2. Press the X button to display the label list.
3. Use the S and T buttons to scroll through the list
and highlight the desired label.
You may need to scroll up or down to view all possi-
ble labels.
4. Use the X button to accept the highlighted label
and exit the list.
NOTE: The label names in list order are: Sensor, Boiler,
Outdoor, Duct, Dischrg, Chiller, Room, Supply,
Return, and Animals.
ENTER
MINIMUM
VALUE FOR
SENSOR A
SETUP
SENSORS
SENSOR A
MIN VAL
0.0
F
o
M24592A
ENTER
MAXIMUM
VALUE FOR
SENSOR A
SETUP
SENSORS
SENSOR A
MAX VAL
0.0
F
o
SETUP
SENSORS
SENSOR A
MIN VAL
OR
MAX VAL
SETUP
SENSORS
SENSOR A
CALIBRATE
ENTER
VALUE TO
CALIBRATE
SENSOR A
SETUP
SENSORS
SENSOR A
CALIBRATE
0.0
F
o
M24594
SETUP
SENSORS
SENSOR A
LABEL
SETUP
SENSORS
SENSOR A
LABEL
SELECT
LABEL FOR
SENSOR A
SENSOR A
BOILER A
OUTDOOR A
DUCT A
DISCHRG A
CHILLER A
ROOM A
M24595
Page view 15
1 2 ... 11 12 13 14 15 16 17 18 19 20 21 ... 39 40

Comments to this Manuals

No comments