T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
63-4368 22
Table 15. Identifying Five Most Recent T7350 Alarms.
The five most recent T7350 alarms are identified in the manufacturer defined output network variable nvoAlarmLog.
nvoAlarmLog Field Description
alarm1 Alarm log: Most recent alarm.
Alarm Codes
0: AT_NO_ALARM (power up value)
1: AT_INVALID_SUBBASE_TYPE
2: AT_NETWORK_COMM_FAIL
3: AT_SENSOR_FAIL
4: AT_INVALID_IO_CONFIG
5: AT_COVER_COMM_FAIL
6: AT_COVER_SUBBASE_MISMATCH
Return to Normal Codes
-127: AT_rtnINVALID_SUBBASE_TYPE
-126: AT_rtnNETWORK_COMM_FAIL
-125: AT_rtnSENSOR_FAIL
-124: AT_rtnINVALID_IO_CONFIG
-123: AT_rtnCOVER_COMM_FAIL
-122: AT_rtnCOVER_SUBBASE_MISMATCH
-1: AT_ALARM_NOTIFY_DISABLED
alarm2
Alarm log: 2
nd
most recent alarm.
0: No alarm (power up value).
alarm3
Alarm log: 3
rd
most recent alarm.
0: No alarm (power up value).
alarm4
Alarm log: 4
th
most recent alarm.
0: No alarm (power up value).
alarm5 Alarm log: Oldest alarm.
0: No alarm (power up value).