Honeywell T7350 User Manual Page 31

  • Download
  • Add to my manuals
  • Print
  • Page
    / 44
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 30
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
31 63-4368
XL15C
Application Object Application Input
Source T7350H
Network Variable Network Variable Field
nvoData2 stagesActive
Logic Loop DCAO Digital Input nvoAlarmStatus CoverCommFail
OR Digital Input nvoAlarmStatus InvalidIOConfig
AND Digital Input nvoAlarmStatus SensorFail
nvoAlarmStatus networkCommFail
nvoAlarmStatus InvalidSubBaseType
nvoError errLoclSpaceSensr
nvoError ErrRemtSpaceSensr
nvoError ErrNetSpaceSensr
nvoError ErrLoclHumSensr
nvoError ErrRemtHumSensr
nvoError errNetHumSensr
nvoError ErrRemtOdSensr
nvoError ErrNetOdSensr
nvoError ErrRemtSetPt
nvoError ErrDischSensr
nvoError errIOConfig
nvoError errSubBaseType
nvoError errSubBaseVerMisMatch
nvoError errNviSpaceTemp
nvoError errNviOccSchedule
nvoError errNviOccSensor
nvoError errnviApplicMode
nvoError errnviOutdoorTemp
nvoError errnviSpaceRH
nvoError errNviBypass
nvoError errNviDLCShed
nvoData2 RelayHeat3
nvoData2 RelayCool3
nvoData2 RelayHeat2
nvoData2 RelayCool2
nvoData2 Relay Aux
nvoData2 RelayHeat1
nvoData2 RelayCool1
nvoData2 RelayFan
nvoData2 dehumidActive
Control Loop SetPtOverride Digital Input nvoAlarmStatus CoverCommFail
LoopDisable nvoAlarmStatus InvalidIOConfig
Bypass Input nvoAlarmStatus SensorFail
OccupancySensor nvoAlarmStatus networkCommFail
nvoAlarmStatus InvalidSubBaseType
nvoError errLoclSpaceSensr
nvoError ErrRemtSpaceSensr
nvoError ErrNetSpaceSensr
nvoError ErrLoclHumSensr
Table 20. Network Connections to XL15C AP Inputs. (Continued)
T7350H Network Variable Outputs can be used as inputs to XL15C application objects.
Page view 30
1 2 ... 26 27 28 29 30 31 32 33 34 35 36 ... 43 44

Comments to this Manuals

No comments