Honeywell 301c User Manual Page 31

  • Download
  • Add to my manuals
  • Print
  • Page
    / 228
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 30
M-510324 301C User Manual 29
7/10 Honeywell
System Programming
Tx Info Menu
COM Menu
This screen displays the selected communication protocol for device
addresses from 1 to 96. Each transmitter’s protocol is defined by the
controller (see Network Auto-configuration section)
.
If a transmitter is compatible with several different protocols, it can be
modified using to one of the following options:
•Vulbus
Mdbs ASCII 7D 2S NP 9600 bauds
Mdbs RTU 8D 2S NP 9600 bauds
Mdbs RTU 8D 1S NP 9600 bauds
Mdbs RTU 8D 1S OP 9600 bauds
When a transmitter is configured with the Modbus communication
protocol, the transmitters automatically sends the programmable
parameters to the controller.
Note: Vulbus transmitter parameters must be programmed manually.